LAARS Pennant PNCV (Sizes 500-2000) - Install and Operating Manual User Manual

Page 49

Advertising
background image

Pennant

(500-2000)

Page 49

and boilers ordered with low temperature controls. To

replace the switch, shut off the 120-volt power to the

appliance. Remove the cover from the switch to access

the mounting screws. Remove the screws, and pull the

switch off the control panel. Remove the capilliary

and bulb from the thermal well located in the header.

Replace in reverse order.

7.2.6 Temperature Control

The temperature control is a Laars LHSC. To

replace the control, shut off the 120-volt power to

the appliance. Remove the cover from the control

panel, and remove the mounting screws to remove the

controller. Replace in reverse order.

7.2.7 Ignition Controls

The ignition controls ensure the proved

interrupted-type ignition system. They control the

hot surface ignitors and prove that the flame signal

is appropriate for powering the gas valves. It also

controls the blower’s pre-purge and post-purge.

Pennant sizes 500 and 750 have one ignition control.

Sizes 1000 to 2000 have two ignition controls. On

sizes 1000, one ignition control controls stages 1 and

2, and the second ignition control controls stage 3. On

sizes 1250–2000, one ignition control is for stages 1

and 2, and the other is for stages 3 and 4.

To replace a control, shut off the 120-volt power

to the appliance. Remove the cover from the control

panel. Remove the electrical connectors from the

ignition control. Take out the controller’s mounting

screws, and pull the controller out. Replace in reverse

order.

7.2.8 Ignitors

The ignitors used are 120v “Hot Surface” type.

They are energized whenever there is a call for heat

and switched off when ignition is established and the

flame has been sensed. Pennant sizes 500 and 750 have

one ignitor. Sizes 1000 to 2000 have two ignitors. To

replace the ignitor, shut off the 120-volt power to the

appliance, remove the ignitor access panel, disconnect

the Molex connector, remove the two mounting screws

on the ignitor flange, and pull the ignitor out. Install in

reverse order, always using a new ignitor gasket with

the replacement ignitor.

Caution

Ignitor gets hot.

7.2.9 Ignition Sensors

The ignition sensors ensure that the main flame

is ignited, so that raw gas is not allowed to fill the

combustion chamber. Pennant sizes 500 and 750 have

one sensor. Sizes 1000 to 2000 have two sensors (one

for each ignition control). The ignitors are the ignition

sensors on Pennant appliances. There are no separate

ignition sensors.

7.2.10 Transformer

The Pennant’s transformer is not capable of

supplying control voltage for external devices such

as zone valves, which must have their own separate

power supply. Should a transformer need replacing,

shut off the 120-volt power. Unplug the transformer

wires, remove the mounting screws and remove the

transformer. Replace transformer in the reverse order.

7.2.11 Blowers

The combustion air blowers bring the combustion

air for the Pennant from the upper chamber to the

lower chamber. Mixing of the gas and air occurs in

the burners. Sizes 500, 750 and 1000 each have one

blower, and sizes 1250 to 2000 each have two blowers

(one blower for stages 1 and 2, and one for stages 3

and 4). If a blower change is required, turn off the

120-volt power and gas supply to the unit. Remove

the front panel. Disconnect the blower's wire harness.

Remove the screws at the blower flange, and pull the

blower out. Replace blower in reverse order, ensuring

that all joints are made correctly. After replacement,

ensure that the unit operates properly, by following the

set-up procedure in this manual.

7.2.12 Flow Switch

The Pennant uses a paddle-type flow switch to

ensure that the unit has water flow before ignition is

allowed.

7.2.13 Heat Exchanger Coil

WARNING

Black carbon soot buildup on a dirty heat exchanger

can be ignited by a random spark or flame, thereby

creating a risk of fire or explosion.. To prevent this

from happening, dampen the soot deposits with a

wet brush or fine water spray before servicing the

heat exchanger.

The Pennant has a pre-mixed burner system.

These systems provide the burners with sufficient air

for complete combustion, and black carbon sooting

is seldom experienced. If sooting is suspected, view

ports for inspection of the heat exchanger are provided

on both sides of the boiler. They are located below the

headers, and are accessed by opening the small round

cover that is attached by one screw. In the unlikely

event that there is a buildup of black carbon soot

or other debris on the heat exchanger, clean per the

following:

1. Disconnect the electrical supply to the unit.

2. Turn off the gas supply by closing the manual gas

valve on the heater.

3. Disconnect and remove the wires, conduit and

sensors from all components that are attached to

the inlet/outlet header.

4. Isolate the heat exchanger from the water supply.

5. Disconnect header flanges from inlet and outlet.

Advertising
This manual is related to the following products: