Page 17

If the water at the inlet of the copper heat

exchanger is less than 140°F (60°C), water from the

outlet of the copper heat exchanger will be directed

back to the inlet of the copper heat exchanger, and will

mix to bring the inlet water up to 140°F (60°C). Once

through the copper heat exchanger, the water picks up

another 20-25°F (11-14°C) (when at high fire), and

it leaves the boiler at 160-165°F (71-74°C). This hot

water is then sent to the system.

If the water at the inlet of the copper heat

exchanger is 140°F (60°C), or higher, the water will be

allowed to flow through the copper heat exchanger and

directly to the outlet of the Rheos+, and there will be a

20-25°F (11-14°C) temperature rise between the inlet

and outlet of the unit, when the unit is at high fire.

The pump in the heater is sized for the heater’s

heat exchangers, the internal mixing system, and 30

feet of full-sized piping, with a normal number of

fittings taken into consideration.

The minimum inlet water temperature for the

Rheos+ is 50°F (10°C) to avoid condensing on the

copper coils.

Figure 5 - Hydronic Piping — Multiple Boilers (Alternate)

5