LAARS Rheos+ RHHV - Install and Operating Manual User Manual

Page 8

Advertising
background image

Rheos+ Boiler and Water Heater

Page 7

Figure 1 - Dimensional Drawing

Model

Intake

Exhaust

Intake

Exhaust

Size

Size

Maximum Run

Maximum Run

1200

6" (15 cm) dia.

6" (15 cm) dia.

50 linear feet with 5 elbows

50 linear feet with 5 elbows

1600

8" (20 cm) dia.

6" (15 cm) dia.

50 linear feet with 5 elbows

50 linear feet with 5 elbows

2000

8" (20 cm) dia.

7" (18 cm) dia.

50 linear feet with 5 elbows

50 linear feet with 5 elbows

2400

8" (20 cm) dia.

10" (25 cm) dia.

50 linear feet with 5 elbows

50 linear feet with 5 elbows

Table 2 - Vent / Air Pipe Sizes

1.8 Locating Appliance for Correct Vent

Distance From Outside Wall or

Roof Termination

The forced draft combustion air blower in the

appliance has sufficient power to vent properly when

the guidelines in Table 2 are followed.

NOTE: When located on the same wall, the Rheos+

combustion air intake terminal must be installed
a minimum of 12" (30cm) below the exhaust vent

terminal and separated by a minimum of 36 inches

(91cm) horizontally.

Model

“V”

Vent Outlet

Connection

“A”

Air Inlet

Connection

“W”

Water

Inlet/ Outlet

Connection

“G” Gas Connects.

Control Packages

“B”

Std & A

Nat/ LP

B & E

Nat

B & E

LP

inches

cm

inches

cm

NPT

NPT

NPT

NPT

inches

cm

1200

6

15

6

15

2-1/2”

1’

1-1/2’

1-1/2”

34-1/4”

87

1600

6

15

8

20

2-1/2”

1-1/2’

2”

2’

34-1/4”

87

2000

7

18

8

20

3”

1-1/2’

2”

2”

34-1/4”

87

2400

10

25

8

20

3”

1-1/2”

2”

2”

32”

81