LAARS Rheos+ RHHV - Install and Operating Manual User Manual

Page 30

Advertising
background image

Rheos+ Boiler and Water Heater

Page 29

The second menu “Add” has to do with the N2

address. Pressing enter when “Add” is displayed will

display “255”, which stands for 255 unique addresses.

The up and down arrows change this value, and enter

saves the value if it is changed.

Changing the “Add” value will have no affect

on the Rheos+, unless a communications card as

been built onto the unit. If a Rheos+ unit has been

ordered with an optional communications card,

more menus will be active, and the unit will come

with separate instructions.

5.7 External Control Connections

Rheos+ units are built with a selector switch and

a terminal strip to allow the Rheos+ to receive a

0-10VDC signal from an external controller (such as a

building automation system or multiple boiler control).

When the selector switch is in the “Rheos+

Control” position, the Rheos+ will be modulated by

the unit’s factory-mounted modulating control.

When the switch is in the “External Control”

position, the unit look for a 0-10VDC signal from an

external (field-supplied) controller.

To interlock the external boiler control with the

Rheos+, the call for heat signal MUST be connected

to the field interlock terminal strip on the Rheos+

(shown in Figure 29). Be sure to remove the factory-

installed jumper between the field interlock terminals.

The 0-10VDC modulating signal MUST be connected

to external control terminal strip, located to the right

of, and behind the front panel. The terminal strip is

labeled “0-10VDC +” and 0-10VDC –” to indicate

which terminal received the hot signal (+) and which

terminal receives the common signal (-) from the

controller.

The Rheos+ unit will modulate between 2.23V

and 10V (for 25% and 100%, respectively). Anything

less than 2.23 volts will result in 25% of full fire.

For the external control to modulate the Rheos+,

the selector switch on the front panel must be in the

“External Control” position.

Important Note: DO NOT MAKE/BREAK RHEOS+

LINE VOLTAGE TO SIGNAL CALL FOR HEAT. A

“call for heat / end call for heat” MUST be connected
to the field interlock terminals. The Rheos+ does not

recognize 0 volts as a signal to shut off. If the call

for heat is not connected between the field interlock
terminals, the Rheos+ will remain in low fire when it

sees 0 volts as a modulating signal.

Caution

Rheos+ supply voltage must not be disengaged,

except for service or isolation, or unless otherwise

instructed by procedures outlined in this manual. To

signal a call for heat, use the 24V field-interlock, as
shown in the wiring diagram(s).

Some Rheos+ components are designed to have

constant voltage during normal operation. If Rheos+

supply voltage is toggled as a call for heat signal,

premature failure of these components may result.

5.8 Wiring Diagrams

Caution

Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous

operation. Verify proper operation after servicing.

Advertising
This manual is related to the following products: