shutoff valve. Remove the front and right-side panels

from the unit. Disconnect the union between the valve

body and the blower. Label the four pressure tubes

that are connected to the valve actuator, to ensure

that they will be replaced correctly. Remove the

valve actuator, per the instructions above. Unscrew

the valve body from the gas train. After the valve has

been removed, replace with a new valve in the reverse

order. Turn on gas shutoff valve and 120 volt power

and check appliance operation and tightness of gas

valve connections.

7.2.4

Safety Gas Valve

The safety gas valve is a 24-volt diaphragm

valve. It is designed to operate with supply pressures

of 4-13 inches w.c. (1.0 to 3.2 kPa). To remove the gas

valve, shut off 120-volt power. Shut off the main gas

supply to the unit. Disconnect the gas supply piping

from the back of the unit. Disconnect the electrical

wires from the valve, and unscrew the gas valve from

the gas train. Re-assemble in reverse order. A bleed

line from the diaphragm type automatic valve shall be

vented per local code requirements.

7.2.5

Manual Reset High Limit Control

The high limit switch is manual reset switch with

an adjustable set point, up to 240°F (116°C) on boiler

models and 200°F (93°C) water heater models. To

replace the switch, shut off the 120-volt power to the

appliance. Remove the cover from the switch to access

the mounting screws. Remove the screws, and pull the

switch off the control panel. Replace in reverse order.

7.2.6

Temperature Control

The temperature control consists of an adjustable

electronic control and digital display module. To

replace the control or the display, shut off the 120-

volt power to the appliance. Remove the cover from

the control panel, and remove the screws from the

DIN rail clip, to which the controls are mounted. Pull

the electrical connector from the controller. Slide the

controllers from the DIN rail clip. Replace in reverse

order.

7.2.7

Auto Reset Temperature Limit

The auto reset temperature limit has a 200°F

(93°C) setting. The is mounted directly onto the

Rheos+ header, on the inlet to the copper coil. It

senses the inlet water temperature to copper coil, and

guards against a malfunctioning mixing system. To

replace the switch, shut off the 120-volt power to the

appliance. Remove the cover from the switch to access

the mounting screws. Remove the screws, and pull the

switch off the control panel. Replace in reverse order.

7.2.8

Mixing Control

The FX05 mixing control is the device that

controls the position of the mixing valve system. This

control is factory set, and must not be adjusted, except

for the °F or °C choice. To remove the control, unplug

the wires from the back, push on the tabs to slide the

clasping mechanism off, and pull the controller out

through the front of the panel. Replace in reverse order.

7.2.9

Mixing Valves

There are two 2-way mixing valves that are

linked and connected to a valve actuator to create the

3-way mixing system. To remove the upper right

valve, remove the actuator and then remove the 2 bolts

that connect the sheet metal to the valve. Remove the

linkage from the arm that is welded to the actuator.

Remove the four bolts on the valve, and slide the

valve out. To remove the lower left valve, remove

the 2 bolts that connect the sheet metal to the valve.

Remove the linkage from the arm that is welded to the

actuator. Remove the four bolts on the valve, and slide

the valve out. Reassemble in reverse order.