LAARS Rheos+ RHHV - Install and Operating Manual User Manual

Page 27

Advertising
background image

LAARS Heating Systems

Page 26

is drawing down, the heater will react to sustain a

minimum tank temperature. Boilers generally have

higher differentials than water heaters, to minimize

short cycling (see throttling range). The differential

is set by removing the cover of the A350 control

and adjusting the potentiometer marked “DIFF” (see

Figure 13).

5.5.3

Offset

The offset determines the temperature below the

controller’s setpoint where the throttling range begins.

It offsets the throttling range.

For instance, if the setpoint is 120°F (49°C) and

the offset is 5°F (3°C), then the unit’s throttling range

will begin at 115°F (46°C). Between 115°F (46°C) and

120°F (49°C), the Rheos+ will be in low fire.

The offset can be adjusted between 0°F and 30°F

(0°C and 17°C) by removing the cover of the S350P

control and adjusting the Offset dial (see Figure 14).

5.5.4

Throttling Range

The throttling range allows the Rheos+ to match

the BTU demands of varying systems, by allowing the

user to choose the temperature range through which

the unit will modulate. This will tell the controller how

fast to respond to a change in temperature. A small

throttling range keeps the unit in high fire more, and

quickens the response of the system. A larger throttling

range allows the Rheos+ to spread its modulating

range over a larger temperature range.

Example, Imperial units: Using a temperature

setpoint of 120°F, with a 20°F differential, a 5°F

offset, and a throttling range of 10°F, the unit will

come on at 100°F and shut off at 120°F. The offset

will set the top of the throttling range 5°F under the

setpoint, which is 115°F in this example. Therefore,

the throttling range will cause the Rheos+ to modulate

between 25% and 100% of full fire between 115°F and

105°F. Between 115°F and 120°F, the unit will remain

at low fire. Between 100°F and 105°F, the unit will be

at full fire.

Example, Metric units: Using a temperature

setpoint of 49°C, with a 11°C differential, a 3°C offset,

and a throttling range of 5°C, the unit will come on at

38°C and shut off at 49°C. The offset will set the top

of the throttling range 3°C under the setpoint, which is

46°C in this example. Therefore, the throttling range

will cause the Rheos+ to modulate between 25% and

100% of full fire between 46°C and 49°C. Between

100°F

38°C

41°C

105°F

43°C

110°F

46°C

115°F

49°C

120°F

100%

75%

50%

0%

25%

Throttling Range

Differential

Offset

Control Parameters:

Setpoint = 120°F / 49°C

Differential = 20°F / 11°C

Offset = 5°F / 3°C

Throttling Range = 10°F / 5°F

Minimum Output = 25% (Factory Setting)

Note: Graph depicts a rise in Rheos temperature after a call for heat. After achieving 120°F/49°C, the Rheos

will not re-energize until the temperature falls below 100°F/38°C.

Rheos+ Inlet Temperature

%

of

Full

Fire

Figure 14 - Control Parameter Graph

Advertising
This manual is related to the following products: