LAARS Rheos+ RHHV - Install and Operating Manual User Manual

Page 46

Advertising
background image

Rheos+ Boiler and Water Heater

Page 45

8.5 Short Cycling — Water Heater

Short cycling will generally occur only in

combination space heating and water heating

applications when the water heater is operating in

the space-heating mode. Because the Rheos+ is a

modulating water heater and its input will reduce when

there is a reduction in heating load, short cycling is

greatly reduced. If the heating load drops below the

minimum input of the water heater for an extended

period, the water heater will have a tendency to short

cycle. If short cycling is frequently experienced,

regardless of the control’s attempt to limit it, the

heating load should be redistributed to control it. See

Section 5.5 regarding controller setup.

If short cycling occurs in a water heater

application, it is probably caused by undersized

piping between the water heater and the storage tank

or by some other factor that restricts proper water

flow through the water heater. The cause should be

determined and corrected.

8.6 High Gas Consumption

Appliances operating with an improper air/fuel

ratio are very inefficient and consequently, have

very high gas consumption. Because efficiency is

high when the CO

2

is high (or O

2

is low), appliances

operating with low CO

2

or high O

2

(especially LP

appliances) consume more gas. Adjust the CO

2

or O

2

for optimum efficiency. If no combustion analyzing

equipment (CO

2

or O

2

) is available then a proper

adjustment of the air/fuel ratio (CO

2

or O

2

) can not

be accomplished. However, by briefly sniffing the

flue gases it is possible to determine if the CO

2

or

O

2

is within the proper range. No significant flue gas

odor should be detected when combustion is proper.

A strong piercing smell indicates poor combustion

and generally a lean mixture - low CO

2

or high O

2

.

The CO

2

should be 8 to 9% at all firing rates. Do not

attempt to correct combustion. Contact factory if the

CO

2

is not within this range.

Section 9

REPLACEMENT PARTS

Only genuine LAARS replacement parts should be

used.

9.1 General Information

To order or purchase parts for the LAARS

Rheos+, contact your nearest LAARS dealer or

distributor. If they cannot supply you with what you

need, contact Customer Service (see back cover for

address, telephone and fax numbers).

Advertising
This manual is related to the following products: