LAARS Heating Systems

Page 6

(12) Firing Mode

F = Modulating

(13) Revision

2 = Second version

(14) Heat Exchanger

E = Glass-lined steel with copper tubes

F = Glass-lined steel with cupronickel tubes

(15) Control Option Code

X = Standard, meets CSD-1 boiler standard

A = Control Pack A: CSD-1, CA, FM, IL, IRI,

Alarm Bell

B = Control Pack B: CSD-1, CA, FM, IL, LDS, MN

F = Non CSD-1

(16) Pump Options

H = Pump mounted, hard water pump

N = Pump mounted, normal pump

S = Pump mounted, soft water pump

(volume water, high efficiency [condensing]

model only)

1.3 Warranty

LAARS Heating Systems’ Rheos+ appliances

are covered by a limited warranty. The owner should

fill out the warranty registration card and return it to

LAARS Heating Systems.

All warranty claims must be made to an

authorized LAARS Heating Systems representative

or directly to the factory. Claims must include the

serial number and model (this information can be

found on the rating plate), installation date, and name

of the installer. Shipping costs are not included in the

warranty coverage.

Some accessory items are shipped in separate

packages. Verify receipt of all packages listed on

the packing slip. Inspect everything for damage

immediately upon delivery, and advise the carrier of

any shortages or damage. Any such claims should be

filed with the carrier. The carrier, not the shipper, is

responsible for shortages and damage to the shipment

whether visible or concealed.

1.4 Dimensions

The overall dimensions are 34.5" (88cm)

wide, 65.75" (167cm) tall, 55" (140cm) deep. Other

dimensions can be found in Figure 1.

1.5 Locating the Appliance

The Rheos+ is for indoor installations only.

The appliance should be located to provide

clearances on all sides for maintenance and inspection.

It should not be located in an area where leakage of

any connections will result in damage to the area

adjacent to the appliance or to lower floors of the

structure.

When such a location is not available, it is

recommended that a suitable drain pan, adequately

drained, be installed under the appliance.

The appliance is design certified by CSA-

International for installation on combustible flooring;

in basements; in closets, utility rooms or alcoves.

Rheos+ Boilers or Water Heaters must never be

installed on carpeting. The location for the appliance

should be chosen with regard to the vent pipe lengths

and external plumbing. The unit shall be installed such

that the gas ignition system components are protected

from water (dripping, spraying, rain, etc.) during

operation and service (circulator replacement, control

replacement, etc.). When vented vertically, the Rheos+

must be located as close as practical to a chimney

or gas vent. If the vent terminal and/or combustion

air terminal terminate through a wall, and there is

potential for snow accumulation in the local area, both

terminals should be installed at an appropriate level

above grade.

The dimensions and requirements that are shown

in Table 1 should be met when choosing the locations

for the appliance:

Appliance

Clearance From

Suggested Service

Surface

Combustible Material

Clearance

inches

cm

inches

cm

Piping Side

1

2.5

18

46

Opposite Side

1

2.5

1

2.5

Top

1

2.5

24

61

Back

1

2.5

36

91

Front

1

2.5

36

91

Vent

per UL1738 venting

system supplier’s

instructions

Table 1 - Clearances

1.6 Locating Pump-Mounted Water Heater

with Respect to Storage Tank(s)

For best results the Rheos+ water heater should

be located within 15 feet (4.6m) of the storage tank(s).

The pump is sized for 30 feet (9.1m) of piping.

Water heater pumps are sized for water hardness;

7.6 to 17 grains per gallon for normal water, greater

than 17 grains per gallon for hard water, and 1 to

7.5 grains per gallon for soft water. If the appliance

must be installed with longer piping runs, then larger

diameter pipe or tubing may be able to be used, in

some instances. Consult the factory for assistance.

1.7 Locating Pump-Mounted Boiler with

Respect to Return/Supply Header

Rheos+ units must be piped in primary-

secondary fashion because of the internal pump and

mixing system.

For the best results the Rheos+ Boiler should

be located within 15 feet (4.6m) of the supply and

return headers. The pump is sized for 30 feet (9.1m) of

piping, in most cases, enough for primary-secondary

piping systems.

If the appliance must be installed with longer piping

runs, then larger diameter tubing may be able to be used,

in some instances. Consult the factory for assistance.