5.5.6 Integration Constant

The proportional control used on the Rheos+ has

internal circuitry that helps to minimize overshoot that

can sometimes be associated with proportional plus

integral (PI) controls. There are three field-selectable

integration constants (slow, medium and fast), and

an off position on the proportional control, which

are selected with the dipswitches on the control (see

Figure 14). In most cases, this setting will not need to

be changed

Off: Switch 1 to ON position and all others to

OFF. Setting the control to the “Off” position puts the

control into proportional only operation. This is not a

recommended setting for the Rheos+.

Slow: Switch 2 to ON position and all others

to OFF. This is the slowest integration constant. It

allows the Rheos+ the most time to reach its setpoint.

In most cases, this is too slow for Rheos+ installations.

Medium: Switch 3 to ON position and all others

to OFF. The integration constant is set to “Medium”

at the factory, and in most cases, will not need to be

46°C and 49°C, the unit will remain at low fire.

Between 38°C and 41°C, the unit will be at full fire.

The throttling range is adjustable between 2°F

and 30°F (1°C to 17°C). The range can be set by

removing the cover of the S350P control and adjusting

the “THROT RANGE” dial (see Figure 14).

5.5.5

Minimum Output Setting

The minimum output setting of the controller is

0% of full fire. However, the minimum output of the

Rheos+ is limited to 25% of full fire by the fan speed

controller, to ensure proper operation of the Rheos+.

If a minimum desired output is higher than 25%, the

setting can be adjusted up by removing the cover of

the S350P control and adjusting the Min Output dial

(see Figure 14). Turning the dial clockwise increases

the minimum output. In most cases, this setting should

be left as shipped from the factory.

100°F

38°C

41°C

105°F

43°C

110°F

46°C

115°F

49°C

120°F

100%

75%

50%

0%

25%

Throttling Range

Differential

Offset

Note: Line with arrows represents what happens after the Rheos+ achieves 120°F/49°C during a call for heat.

It will cool to 110°F/43°C, and will re-energize at less than full fire. The Rheos+ will be at full fire only if the

temperature goes below 105°F/41°C.

Rheos+ Inlet Temperature

%

of

Full

Fire

Control Parameters:

Setpoint = 120°F / 49°C

Differential = 10°F / 5°C

Offset = 5°F / 3°C

Throttling Range = 10°F / 5°F

Minimum Output = 25% (Factory Setting)

Figure 15 - Control Parameter Graph