temperature is less than 140°F (60°C), internal mixing

will keep the outlet temperature at 160-165°F (71-

74°C), and this will mix with the tank temperature

to maintain a lower temperature in the tank. If the

return temperature is 140°F (60°C) or higher, the

outlet temperature of the heater will be the return

temperature plus 20-25°F (11-14°C) when the Rheos+

is at high firing rate.

The manual reset high limit is on the outlet of

the Rheos+. Set the manual reset high limit at about

20°F (11°C) higher than the highest expected outlet

temperature, to avoid nuisance lockouts

5.4.2

Internal Water Heater

Temperature Control

When an external control is not used, the

circulator between the heater and the storage

tank must run continuously, so that the heater’s

temperature control can detect and control the water

temperature in the storage tank. The Rheos+ water

heater’s temperature control is adjusted to its lowest

temperature position when shipped from the factory.

This is the preferred starting point for setting the

temperature control.

The Rheos+ temperature control measures

temperature on the heater inlet, sensing return water

temperature. If the return water temperature is less

than 140°F (60°C), internal mixing will keep the outlet

temperature at 160-165°F (71-74°C), and this will

mix with the tank temperature to maintain a lower

temperature in the tank. If the return temperature is

140°F (60°C) or higher, the outlet temperature of the

heater will be the return temperature plus 20-25°F (11-

14°C) when the Rheos+ is at high firing rate.

The manual reset high limit is on the outlet of

the Rheos+. Set the manual reset high limit at about

20°F (11°C) higher than the highest expected outlet

temperature, to avoid nuisance lockouts.

Caution

Should overheating occur or the gas supply fail to

shut off, turn off the manual gas control valve to the

appliance.

5.5 Temperature Control Features

The Rheos+ temperature control is versatile and

will allow the user to better match the modulating

control to the application. Settings that can be changed

are temperature setpoint, differential, offset, throttling

range, and minimum output.

The temperature setpoint is the setting at which

the unit will shut off, having satisfied the controller’s

call for heat.

The differential determines how far the

temperature in the Rheos+ can fall before

energizing again.

The offset determines where the throttling range

begins.

The throttling range is the temperature range

through which the unit will modulate from minimum

to maximum firing rate.

Important Note: These control parameters work

together. Therefore, setting one parameter may have

an affect on another. Figures 14, 15 and 16 show the
relationships between these settings. Figure 14 follows
the examples that are shown in the following sections,
and Figures 15 and 16 are examples of how the
parameters can interfere with each other.

5.5.1

Temperature Setpoint

The temperature setpoint is the point at which the

temperature control relay will be de-energized and the

unit’s call for heat will end. The temperature setpoint

is adjusted with the setpoint dial on the A350 control

(see Figure 13). The temperature control’s sensor is in

the inlet of the unit.

V C I

Cover Screws

(Quantity=4)

Integration

DIP Switch

is set to

“Medium” at

the factory.

See Section

5.5.6 for

descriptions

of other

settings.

LED Indicator

(Percent of

Output)

Module

Connector

THROT

RANGE

MIN

OUTPUT

OFFSET

Reverse

Acting
Direct

Acting

Operation Mode

Jumper Positions

Figure 13 - Proportional Control

Note: Jumper must be in “Reverse Acting” mode, or Rheos will not

operate properly.

5.5.2

Differential Setting

The differential is the difference in temperature

settings when the temperature control’s relay is

energized and de-energized. For instance, if the

temperature setpoint is 120°F (49°C) and the

differential is 20°F (11°C), the temperature control

will call the unit to energize at 100°F (38°C). (The

differential is the setpoint minus the differential

setting) The call for heat will end when the unit

reaches its setpoint of 120°F (49°C). The Rheos+

differential is adjustable from 1°F to 30°F (1°C to

17°C). In general, the differential setting for a water

heater system will be low, so that when a storage tank