General information for connecting vent pipes, Vermont castings, majestic products: dvr33, Crimped end pipes – Vermont Casting DVR33 User Manual

Page 11: Termination clearances

Advertising
background image

11

Vermont Castings, Majestic Products: DVR33

10004920

General Information for Connecting Vent Pipes

Crimped End Pipes

Before joining elbows and pipes, apply a bead of high
temperature sealant to the crimped end of the elbow or
pipe.

Join the pipes using a 2” (50 mm) overlap and secure
the joints with three sheet metal screws (Fig. 13). Wipe
off excess sealant.

Canadian Installations:

The venting system must be installed in accordance
with the current CSA-B149.1 installation code.

USA Installations:

The venting system must conform to local codes and/
or the current National Fuel Code ANSI Z223.1.

Only venting components manufactured by Vermont
Castings, Majestic Products may be used in Direct
Vent systems.

1" (25 mm) from
crimped end of pipe

Screw

CFM175

Fig. 13 Apply a bead of high temperature sealant.

Outside Corner

Inside Corner

Termination Clearances

Termination clearances for buildings with combustible and noncombustible exteriors.

A =
Combustible
6"(152mm)

Noncombustible
2"(50mm)

B =
Combustible
6"(152mm)

Noncombustible
2"(50mm)

A

Balcony -
with no side wall

G =
Combustible
NonCombustible
12"(305mm)

G

Balcony -
with perpendicular side wall

H = 24"(610mm)

J = 20"(508mm)

H

J

B

Recessed Location

C = Maximum depth of 48"
(1219mm) for recessed
location.

D = Minimum width for back wall
of a recessed location.
Combustible 38"(965mm)
Noncombustible 24"(610mm)

E = Clearance from corner in
recessed location.
Combustible 6"(152mm)
Noncombustible 2"(50mm)

C

D

C

E

V

V

Combustible &
NonCombustible

V

V

V

CFM115

Fig. 12 Termination clearances.