Troubleshooting – honeywell millivolt valve – Vermont Casting DVR33 User Manual

Page 28

Advertising
background image

28

Vermont Castings, Majestic Products: DVR33

10004920

Troubleshooting – Honeywell Millivolt Valve

START

CHECK

Gas Supply ON

Pilot lights with Piezo
igniter

Lockout has engaged. Wait 60
seconds and try again.

For spark at electrode while
depressing Piezo, 1/8" gap
to pilot hood needed.

All wiring connections

Replace Piezo igniter

Supply line hooked up

Shutoff valve OPEN

PILOT STAYS LIT

For air in the lines

Thermopile needs min. 325 mv

Adjust Pilot flame height

All wiring connections

Replace thermopile

Thermocouple needs min. 14 mv

PILOT LIGHTS MAIN
BURNER

Valve is turned ON

Wall switch is not turned ON.
Watch for grounded wires!

Thermopile needs min. 325 mv.

Plugged burner orifice

Defective Valve: Turn to Pilot;
meter should read greater than
100 mv. If not, replace.

SYSTEM OK

YES

NO

NO

NO

NO

YES

YES

YES

Window Frame Assembly Should be Removed Before Service Work