0 operation and service (cont'd) – Reznor ADFH Operation Manual User Manual

Page 12

Advertising
background image

Form O-ADF/RDF, P/N 148385R2, Page 12

3.0 Operation

and Service

(cont'd)

The electronic modulating-type gas controls act in response to discharge and/or room

air temperature sensors to change the gas flow rate to the burner, thus lengthening or

shortening the flame. The BTU output is varied (modulated) to maintain the required

discharge air temperature.
These modulating gas control options are electronic because in all cases the gas valve

acts to adjust the flow of the gas to the main burner in response to DC volts emanat-

ing from an amplifier. When the DC voltage is between 0 and 5 volts, the main valve

seat is closed. Low fire flow is accomplished through a mechanical bypass. The low

fire flow rate is set at the factory and should not need adjustment. However, if adjust-

ment is necessary, refer to the Maxitrol literature that is included in the heater owner's

envelope.
All of the electronic makeup air modulating gas control burner systems include low fire

start. On an initial call for heat, the main burner ignites at its lowest input. During mild

weather, the burner may then cycle off. Such full shutdown can be dictated by the out-

door ambient cutoff control. As the outside air temperature climbs above the setpoint

of the outdoor ambient control, the burner control circuit is de-energized. When mod-

erately cold outside air temperatures exist, the burner will modulate between low flame

and high flame. Low fire start and the outdoor ambient control prevent the makeup air

system from heating already warm air and providing "too much" heat to the building.
For troubleshooting guides and further explanation of Maxitrol Series 14 and 44 elec-

tronic modulation gas control systems, refer to the Maxitrol literature in the owner's

envelope.
The Option AG30, AG31, AG32, and AG35 electronic modulation systems are com-

prised of Maxitrol Series 14 controls for makeup air. Options AG30 and AG31 systems

electronically maintain a constant discharge air temperature in the range of 55-90°F.

Option AG31 includes an overriding thermostat. Option AG32 system will maintain a

constant discharge air temperature in the range of 80-130°F. Option AG35 maintains a

discharge temperature range of 120-160°F.

FIGURE 20 -

Modulating Gas

Valve - Options

AG30, AG31, AG32,

AG33, AG35, AG36

FIGURE 21 - Maxitrol

Series 14 Components

used in Makeup Air Gas

Control Options AG30,

AG31, AG32, AG35

Amplifier, P/N 148590

Temperature

Sensor

Mixing

Tube

Temperature

Selector

Option AG36 is a special application gas train that is designed for controlling the envi-

ronment of a paint booth operation. The system includes a Maxitrol A1494 amplifier,

discharge air temperature sensor, dual remote discharge air temperature selector (dry-

ing selector 80-140°F and a spray selector 60-90°F), and two switches to control the

operation of the modulating gas valve.

FIGURE 22 - Maxitrol

Series 44 Components

used in Makeup Air Gas

Control Option AG33

Amplifier, P/N 157915

Temperature

Sensor,

P/N 119617

Mixing

Tube,

P/N 90323

Temperature

Selector, P/N 86990

3.6 Gas Train Including Burner, Gas Controls, Manifold

Arrangements, and Gas Pressure Switches (cont'd)

Option AG33 electronic modulation system is comprised of Maxitrol Series 44 con-

trols for makeup air. The low limit (20-60°F) and the high limit (60-140°F) for control of

discharge air temperature are set at the amplifier located in the control compartment.

The space temperature is set at the remote selectrastat (55-90°F range) located in

the space. When the temperature is below the space temperature setpoint, the con-

trol system operates the burner to automatically adjust the discharge air temperature

within the maximum and minimum limits set on the amplifier.

Advertising
This manual is related to the following products: