Form O-ADF/RDF, P/N 148385R2, Page 13

• Electronic Modulation Makeup Air Gas Control Option AG37

Amplifier,

P/N 133229

Selector,

P/N 133230

FIGURE 23 - Components of the Gas

Control System used in Option AG36

designed specifically for paint booths

- controls are mounted on a remote

console

Maxitrol

Signal

Conditioner,

P/N 134170

FIGURE 24 - Maxitrol

Signal Conditioner for

Computer Control

Function: Control Option AG37 does not

have a duct sensor or amplifier. Instead, a

Maxitrol signal conditioner is activated by a

customer-supplied input signal (either 4-20

milliamps or 0-10 volt) to control the modula-

tion of the gas valve.

Makeup Air with Recirculation Air Gas Control Systems (RDF only)
• Electronic Modulation Makeup Air with Recirculation Gas Control

Options AG47, AG48, and AG51

Refer to the wiring diagrams in the main electrical box to determine which controls

are on the system being serviced.

NOTE: All field-supplied control wiring for Maxitrol

controls must

not be run inside conduit with line voltage wiring. To avoid any potential

electrical interference, all field-supplied wiring for Maxitrol controls should be shielded

wiring and must be grounded at the unit only.
Function: These makeup air with recirculation gas control systems provide a mix

of outside and recirculated air heated to a temperature controlled by a discharge air

sensor. Each system is equipped with electronic modulation controls that modulate

burner flame from 1/25th of full fire input to full fire and adjust the outside air damper in

response to outside and return air sensors.

Both the flow of the gas to the main burner and the outside (bypass) air damper posi-

tion are adjusted in response to DC volts emanating from an amplifier. When the DC

voltage is between 0 and 5 volts, the main valve seat is closed. Low fire gas flow

is accomplished through a mechanical bypass. Minimum outside air is 25%. Carbon

dioxide (CO

2

) in the discharge air of the unit is maintained to a level in compliance with

ANSI Z83.18 requirements.

For troubleshooting guides and further explanation of Maxitrol Series 14 and 44 elec-

tronic modulation gas control recirculation systems, refer to the Maxitrol literature in the

owner's envelope.
Option AG47 electronic modulation system is comprised of Maxitrol Series 14 controls

for makeup air with recirculation. The system electronically operates the burner and/or

the outside air damper to maintain a constant discharge air temperature in the range

of 40-95°F.

FIGURE 25 -

Modulating Gas

Valve - Options

AG47 and AG48

FIGURE 26 -

Maxitrol Series

14 Components

used in

Recirculation

Air Gas Control

Option AG47

Return Air Sensor,

P/N 204452

Outside Air Sensor,

P/N 204452

Amplifier, P/N 204454

Selector,

P/N 204455

Discharge

Air Sensor,

P/N 204453

Option AG48 electronic modulation system is comprised of Maxitrol Series 44 controls

for makeup air with recirculation. The low limit (20-60°F) and the high limit (60-140°F)

for control of discharge air temperature are set at the amplifier. The space tempera-

ture is set at the remote selectrastat (55-90°F range) located in the space. When the

temperature is below the space temperature setpoint, the control system operates the

burner and/or the outside air damper to automatically adjust the discharge air tempera-

ture within the maximum and minimum limits set on the amplifier.