3 limit safety controls, 4 air pressure switches – Reznor ADFH Operation Manual User Manual

Page 9

Advertising
background image

Form O-ADF/RDF, P/N 148385R2, Page 9

Column of 13

indicator bulbs;

always replace

burned out bulbs,

P/N 125189.

Control Circuit Power

Control Switch Energized

Firestat Normal

Freezestat Normal

Starter Energized

Blower ON - Low Air Pressure Normal

Blower ON - High Air Pressure Normal

Manual and Auto Limits

Normal
Outside Air Cutoff Normal
Low Gas Pressure Normal
High Gas Pressure Normal
Pilot Valve Energized
Gas Safety Valve Energized

FIGURE 10 - Diagnostic Circuit Board, P/N 151263

3.3 Limit Safety

Controls

Each unit has an automatic temperature activated limit control, a manual reset tem-

perature activated limit control, and an electrical activated energy cutoff device.

• Automatic Reset Limit Control

Function: If the temperature of the discharge air reaches the setpoint, the limit will

open the circuit to the burner system and close all burner and pilot valves. The limit

control will be activated if total airflow is reduced or if gas pressure surges at the burner

causing excessive discharge air temperature. The system will restart when the dis-

charge air temperature decreases below the setpoint.
Service: Failure of this limit requires replacement of the control.

FIGURE 11 -

Automatic

Reset Limit

Controls

Model

P/N

Setting

RDF

86979

135°F

ADF

122856 130°F

ADFH

57953

170°F

• Manual Reset Limit Control

Function: The manual reset limit has a higher setting than the automatic limit and

requires manual resetting to restart the system. If for any reason the automatic limit

should fail to protect against overheating, the manual limit will shutdown the system.

Should the manual reset limit activate, check the entire system to determine the cause.

Make any necessary changes or adjustments before restarting the burner system.

Restart of the unit can be done only after the limit has been cooled and the reset but-

ton depressed.

CAUTION: If the manual reset limit activates, find and correct the

cause before restarting the system.

Service: Failure of this limit requires replacement of the control.

FIGURE 13 - ECO Limit

Control

Setting

305°F

FIGURE 12 - Manual

Reset Limit Controls

Model RDF -

Setting 150°F,

P/N 82610

Model ADF -

Setting 135°F,

P/N 122858;

Model ADFH -

Setting 175°F,

P/N 122990

• Emergency Cut Off Limit Control

Function: The emergency cut off is a fusible link high temperature limit which pro-

vides onetime redundant protection against overheating. If the temperature sensitive

limit controls malfunction, the electrically activated emergency cutoff will shutdown the

system.
Service: If this limit activates, the manual limit control has failed and must be replaced.

The cause for activating the emergency cut off limit control must be found and cor-

rected before re-starting the system.

P/N 82414

3.4 Air Pressure

Switches

Location: Control Compartment Electrical Box (See FIGURE 9.)

• Low Airflow Switch

Function: The low airflow switch is a velocity pressure switch that monitors airflow

across the burner. Until the airflow attains adequate volume for combustion, the switch

remains open. When the switch recognizes adequate air volume, it closes, permitting

both the pilot and burner to operate. Low pressure switch is normally open; it closes on

pressure rise at .25" w.c. Do not alter or adjust setting.

Reset Button