3.0 Operation and Service (cont'd)

3.9 Troubleshooting

Chart 1 - System Troubleshooting (Check the diagnostic lights.)

Symptom or Problem

Cause and Remedy

1. Disconnect switch is closed, but "control power" light is

not lit.

1. Fuses are missing or blown in disconnect switch - replace fuses.

2. Transformer not wired according to diagram - check wiring.

3. Secondary 8A fuse (on transformer) is missing or blown - replace fuse.

4. Indicator light is burned out - replace bulb (P/N 125189).

2. Disconnect switch is closed, but "firestat normal" light is

not lit.

1. See causes and remedies for Problem 1 above.

2. Optional control relay or door switch contacts are open - to test, jump terminals 3 to 4

or 1 to 2

3. Firestat option not ordered - verify order/wiring diagram.

4. Firestat manual reset tripped - reset firestat control.

3. Disconnect closed, blower switch in test position, "firestat"

light is lit, but "freezestat" light is not lit

1. Freezestat option not ordered - verify order/wiring diagram.

2. Freezestat relay contacts are open - checking setting on control.

3. Indicator bulb is burned out - replace bulb (P/N 125189).

4. Disconnect closed, blower switch in test position, "firestat"

and "freezestat" lights are lit, but "starter energized" light is

not lit and the blower motor is not operating.

1. End switch on damper motor not closed. - check end switch wiring.

2. Faulty damper relay - replace relay.

3. Damper motor miswired - rewire damper motor per wiring diagram.

5. Disconnect closed, blower switch in test position, "fires-

tat", "freezestat" and "starter energized" lights are lit, but the

blower motor is not operating.

1. Blower motor not wired correctly - check wiring diagram on motor.

2. Faulty motor starter - replace (check coil first).

3. Faulty blower motor relay - replace relay.

6. Disconnect closed; blower switch in test position; "fires-

tat", "freezestat" and "starter energized" lights are lit and the

blower motor is operating; but the "low air light" is not lit.

1. Low air switch open - verify pressure drop at burner.

2. Indicator light is burned out - replace bulb (P/N 125189).

3. Faulty low air switch - replace pressure switch (P/N 203932).

7. Disconnect closed; blower switch in test position; "fires-

tat", "freezestat", "starter energized" and "low air" lights are

lit and the blower motor is operating; but the "high air light"

is not lit.

1. High air switch open - verify pressure drop at burner.

2. Indicator light is burned out - replace bulb (P/N 125189).

3. High air switch option not ordered - verify order/wiring diagram.

4. Faulty high air switch - replace pressure switch (P/N 203933).

8. Disconnect closed; blower switch in test position; "fires-

tat", "freezestat", "starter energized", "low air" and "high air"

are lit; but the "limit control normal" light is not lit.

1. Indicator light is burned out - replace bulb (P/N 125189).

2. Tripped manual reset limit control(s) - reset manual control.

3. Faulty manual limit control (s) - replace limit control.

9. Disconnect closed; blower switch in test position; "fires-

tat", "freezestat", "starter energized", "low air", "high air" and

"limit control normal" lights are lit; but the "ambient (outside

air) cutoff normal" light is not lit.

1. Indicator light is burned out - replace bulb (P/N 125189).

2. High ambient control option not ordered - verify order/wiring diagram.

3. High ambient control contacts open - check setting on control.

10. Disconnect closed; blower switch in test position; "fir-

estat", "freezestat", "starter energized", "low air", "high air",

"limit control normal" and "ambient (outside air) cutoff nor-

mal" lights are lit; but the "low gas pressure normal" light is

not lit.

1. Indicator light is burned out - replace bulb (P/N 125189).

2. Low gas pressure switch option not ordered - verify order/wiring diagram.

3. Low gas pressure switch contacts open - check setting on control.

4. Low gas pressure switch contacts open - check gas pressure.

5. Faulty gas pressure switch - replace gas pressure switch.

11. Disconnect closed; blower switch in test position; "fir-

estat", "freezestat", "starter energized", "low air", "high air",

"limit controls normal", "ambient (outside air) cutoff normal"

and "low gas pressure normal" lights are lit; but the "high

gas pressure normal" light is not lit.

1. Indicator light is burned out - replace bulb (P/N 125189).

2. High gas pressure switch option not ordered - verify order/wiring diagram.

3. High gas pressure switch contacts open - check setting on control.

4. High gas pressure switch contacts open - check gas pressure.

5. Manual reset on switch tripped - reset pressure switch manual reset.

6. Faulty gas pressure switch - replace gas pressure switch.

12. Disconnect closed; blower and burner switches in

run position; control switch is in "winter" position; "control

power", "high gas normal"; "low gas normal"; "firestat nor-

mal"; "system switch energized"; "starter energized" and

"freezestat normal" lights are lit; but igniter is not becoming

energized or beginning to glow.

1. Lack of power at L1 on ignition module - ECO blown, find cause then replace ECO.

2. Faulty burner enable relay - replace relay.

3. Low stage relay contacts are not closed - check air controller or thermostat setting.

4. Faulty low stage relay - replace relay.

5. Faulty hot surface ignitor - check continuity at the ignition module and circuit board. If

reading is greater than 5-6 ohms, replace ignitor.

6. Faulty ignition module - replace entire module.

13. Disconnect closed; blower and burner switches in

run position; control switch is in "winter" position; "control

power", high gas normal; "low gas normal"; "firestat normal";

"system switch energized"; "starter energized" and "freez-

estat normal" lights are lit; ignitor glowing but "pilot valve

normal" light (thus the pilot valve) is not energized.

1. Ignitor not reaching 1.4A threshold - check voltage and current to ignitor.

2. Faulty hot surface ignitor - check continuity, replace ignitor.

3. Faulty ignition module - replace entire module.

14. Disconnect closed; blower and burner switches in

run position; control switch is in "winter" position; "control

power", high gas normal; "low gas normal"; "firestat normal";

"system switch energized"; "starter energized" and "freez-

estat normal" lights are lit; ignitor has reached 1.4A and has

opened the pilot valve bringing on the "pilot valve normal"

light; but the pilot flame is not present. (After two trials the

unit will go into safety lockout requiring cycling of the main

disconnect switch.)

1. Air in pilot gas line - bleed pilot line.

2. Inadequate pilot gas pressure - verify pilot gas pressure (3.5" w.c.)

3. Faulty pilot valve - replace pilot solenoid valve.

4. Faulty ignition module - replace entire module.