FIGURE 29 - Gas

Pressure Switches

Low Gas Pressure

Switch, P/N 204375
(automatic)

High Gas Pressure

Switch, P/N 204297

(manual reset)

3.7 Inlet Air

Controls

Description: The system is equipped with one of the 11 types of inlet air control

arrangements listed below. All systems provide a constant flow of outside air across

the burner at the required air volume (CFM). Refer to the wiring diagrams in the main

electrical box to determine which controls are on the system being serviced.

Option AR1 - a constant supply of 100% makeup air

Option AR19 - 100% outside makeup air with variable supply air volume (CFM).

The discharge damper controlling the variable air supply is controlled by a manually

set remote potentiometer and can be varied from 100% to 20-25% of total rated airflow

(CFM). In response to changes in the discharge damper setting, the bypass damper

balances the volume of air so that the required fixed amount of air volume flows over

the burner.

Option AR20 - 100% outside makeup air with variable supply air volume (CFM).

The discharge damper controlling the variable air supply is automatically controlled

by a building pressure sensor and can be varied from 100% to 20-25% of total rated

airflow (CFM). In response to changes in the discharge damper setting, the bypass

damper balances the volume of air so that the required fixed amount of air volume

flows over the burner.

Option AR22 - a combination of outside makeup air and bypass return air includ-

ing modulating return air and bypass air dampers. The volume of outside air is regu-

lated by a remotely located, manually set potentiometer.

Option AR23 - a combination of outside makeup air and bypass return air includ-

ing modulating return air and bypass air dampers. The volume of outside air is regu-

lated automatically by a remotely located building pressure sensor.

Option AR33 - 100% outside makeup air with variable supply air volume (CFM).

The discharge damper controlling the variable air supply is automatically controlled by

a 0-10 VCD or 4-20 milliamp signal. In response to changes in the discharge damper

setting, the bypass damper balances the volume of air so that the required fixed

amount of air volume flows over the burner.

Option AR34 - a combination of outside makeup air and bypass return air includ-

ing modulating return air and bypass air dampers. The volume of outside air is regu-

lated by a 0-10 VCD or 4-20 milliamp signal.

Option AR36 - 100% outside makeup air with variable supply air volume (CFM).

The discharge damper controlling the variable air supply is automatically controlled

by a remotely located photohelic pressure sensor. In response to changes in the dis-

charge damper setting, the bypass damper balances the volume of air so that the

required fixed amount of air volume flows over the burner.

Option AR37 - a combination of outside makeup air and bypass return air includ-

ing modulating return air and bypass air dampers. The volume of outside air is regu-

lated by a remotely located photohelic pressure sensor.

WARNING: Burner

profile plates are

factory set to match

CFM requirements.

Do not adjust profile

plates without

contacting your

Sales Representative

for technical

assistance.

(

NOTE: Both high and low gas pressure switches incorporate a vent limiting device

and do not require venting to the outdoors when used in an indoor installation.)

Airflow Dampers

Function: Dampers operate in response to controls to provide the rated flow of makeup

air to the building. Minimum outside air is 20-25%.
Service: Clean all dampers of dust or dirt.

FIGURE 30 -

Damper

Motor

Function: The damper motor automatically actuates the return air, bypass, and/or

discharge dampers in response to an electrical control device. The damper motor is

direct-coupled to the dampers so there is no damper linkage to adjust.
Service: There is no service required on these motors other than external cleaning. If

the motors need replaced, replace with an identical damper motor.