Reznor ADFH Operation Manual User Manual

Page 5

Advertising
background image

Form O-ADF/RDF, P/N 148385R2, Page 5

S

2.3.4 Air

Pressure

Profile plate sensing tubes should be checked quarterly and cleaned no less than

semi-annually. If the sensing tubes become even partially blocked, false pressure

readings may be relayed.
To clean, remove the screened end caps and clean the screens and the tubes. Replace

the clean end caps. Check the pressure differential across the profile plate using a

slope gauge. To attach the slope gauge, open the control compartment door panel.

Just below the junction box, locate the tubing connections. Remove the cap at each

connection and attach the slope gauge using two field-supplied 1/4" x 1/8" female NPT

barbed tubing connections. For instructions on measuring air pressure, see Paragraph

3.4. Air pressure differential should be between -.25" and -.75" w.c.

FIGURE 3 - Circuit Indicator

Board, P/N 151263

Check bulbs

not lit with other

bulbs; replace

any burned out

bulbs.

Row of Bulbs

R

2.3.5 Circuit

Indicator Board

(check lights)

The circuit indicator board is

located in the control compart-

ment electrical box (See

FIGURE

9, page 8). Check operation of all

indicator lights by switching lights

that are not lit with one that is cur-

rently lit. Replace any burned out

indicator bulbs (

P/N 125189).

2.3.6 Main

Burner and Pilot

Assembly

For the most part, the burner and pilot are self cleaning. However, if the application is

extremely dirty or dusty, cleaning of the burner and pilot may be necessary. Inspect the

burner annually. Follow these instructions. If it is necessary to replace any parts, use

only factory-authorized replacements.
1) Turn off the gas and power supply to the system.

2) Remove the door panels in the burner/control cabinet. Locate the pilot.

CAUTION: Wear eye

protection while

pressure cleaning

and drilling.

S

WARNING: Do not

enlarge burner ports

or performance

may be drastically

affected.

FIGURE 4 - Burner

End Plate showing Hot

Surface Ignitor

Flame Sensor (not

shown) Location

Burner

End Plate

NOTE: Model RDF units

manufactured prior to

3/96 have a spark ignition

system. Clean ultraviolet

sensor and spark plug.

Replace as needed.

WARNING: Burner

profile plates are

factory set to match

CFM requirements.

Do not adjust

profile plates

without contacting

your Sales

Representative for

technical assistance.

FIGURE 5 - Direct Fired

Burner

Ignitor

Mixing

Plates

Burner - Full length of

the burner is made up

of a series of 6" or 12"

burner sections.

Burner

End Plate

Pilot Tubing