Reznor ADFH Operation Manual User Manual

Page 7

Advertising
background image

Form O-ADF/RDF, P/N 148385R2, Page 7

45°

Airflow

to S

pace

Out

side

Airflow

Media Pads

Screen

Screen Retainer

Top Pad

Retainer

Screw

Bottom Pad

Retainer

FIGURE 6 - Removal and Replacement of

Evaporative Cooling Module Media

FIGURE 7 -

Media must be

installed

with 45°

angle sloping

downward

toward the

incoming

outside air.

IMPORTANT: The

media is made up of two

different sheets of cooling

material. Each sheet has its own unique angle. When

replacing the cooling media, BE CERTAIN that the 45°

angle slopes downward toward the incoming outside

air (as illustrated above). If the media is not installed

properly, water blowoff from the media pads will occur.

6. Replace media by sliding media pads over both support rails until back stop is encountered. Media

must be

placed as shown in

FIGURE 7.

7. Center screen on the incoming air side of the media.

8. Replace the two side screen retainers by fitting them between the side of the media pad and the side of the cool-

ing module. The retainers should fit snugly, pinching the screen against the media pads.

9. Replace the bottom pad retainer by securing the retainer between the pad and the reservoir pan. Fasten with the

three sheetmetal screws removed in Step 2.

10. Replace the top pad retainer by securing the retainer between the pad and top of the cooling module. Fasten with

the three sheetmetal screws removed in Step 1.

Other Evaporative

Cooling Module

Maintenance

REFERENCE:

Evaporative

Cooling Module

Troubleshooting Guide,

Paragraph 3.9, page 19,

Chart 2.

Water Feed Line and PVC Distribution Piping - Annually, the water supply line and

PVC water distribution pipe should be flushed of debris and contaminants.

1. Remove the media pads following the media replacement instructions.

2. Remove the water feed line from the downstream side of the ball valve and

unscrew the water bleed line barbed hose fitting.

3. Force a fresh water supply through the water inlet hose and thoroughly flush the

distribution pipe.

4. Reassemble being careful to install media with air flow direction as shown in

FIGURE 7.

Water Pump and Inlet Basket Screen (applies to system with float and pump con-

trol) -- Annually, the pump and inlet basket screen should be removed, disassembled,

and cleaned.

WARNING: Do not expose pump motor or any part of the electrical

box to water. Evaporative cooling pump is NOT submersible.

1. Disconnect the power supply to the unit.

FIGURE 8 - Remove

Junction Box, Pump

and Float Switch as an

Assembly

Pump

Motor

Pump with mesh screening over inlet

Float

Switch

Junction Box (Note: Only 208V

unit will have a transformer in

the junction box.)

Advertising