FIGURE 35 -

Door Switch,

P/N 124253

Door Switch (Option BX1)

Location: The control is installed on an overhead door opening to control the opera-

tion of the heater to coincide with the opening and closing of the door.
Function: The function of the switch is to energize and interlock the heating unit when

an outside overhead door reaches approximately 80% of full open travel. The switch

will de-energize the furnace when the overhead door closes approximately 20%. The

complete switch includes a limit switch electrically wired to the heater and a roller yoke

for mechanical activation by a field-supplied trigger on the overhead door.

FIGURE 36 - Dirty Filter

Pressure Switch,

P/N 105507

Dirty Filter Switch (component of Remote Console Option RC14)

Location: Switch is located in the main electrical box (See FIGURE 9); sensor tubes

run to either side of the filter rack; indicator light is on the remote console.
Function: The dirty filter switch is a pressure switch that activates an indicator light

on the remote console when the filters need cleaned or replaced (See Paragraph

2.3.2). This switch is only on systems with an optional console that includes a dirty filter

light. The pressure switch is set during installation so that the light will be activated at

approximately 50% filter blockage. Contacts should close at .17 to 5.0" w.c. ± .05" w.c.
Service: Clean the sensor tubes. If the dirty filter indicator system still does not func-

tion properly, check the setting of the switch. With clean filters in place, blower doors

closed, and blower in operation, decrease the pressure setting by adjusting the set-

screw on the switch clockwise until the filter light is energized or screw is bottomed out.

At that point, adjust the setscrew three full turns counterclockwise or until the screw is

top ended.
If it is determined that the switch needs replacing, use an identical switch. When a new

switch is installed, it must be manually set; follow the instructions above.

Firestat (Option BD2 or BD4)

Location: Firestat in Option BD2 is factory-mounted in the unit. Firestat in Option BD4

is field-mounted on the return air ductwork with the sensor extending into the duct.

This control requires manual reset so it should be mounted in an accessible location.
Function: The firestat will shut down the system if the temperature at the sensor

reaches 200°F. The switch must be manually reset.
Service: Clean the external surface. Check the wiring and connections.

FIGURE 37 -

Firestat,

P/N 42782

FIGURE 38 -

Photoelectric Smoke

Detector (cover

removed), P/N 159553,

used with sampling

tube, P/N 159714

FIGURE 39 - P/N 126170

Photoelectric Smoke Detector (Option SA1)

Location: Field-mounted in the discharge ductwork.
Function: The detector will shut down the system if

smoke is detected in the discharge ductwork.
Service: Clean the external surface. Check the wiring

and connections.

Low Temperature Limit (Freezestat), Option BE2

Location: The control is in the blower section electrical box; the sensing bulb is field-

mounted in the discharge duct.
Function: The freezestat will shut down the system if the discharge temperature falls

below the setpoint. The switch is automatic and will startup the heater when the tem-

perature reaches the setpoint.
Service: Clean the external surface. Check the wiring and connections. Freezestat

Controller is P/N

126170.