0 operation and service (cont'd), Maximum supply pressure by manifold – Reznor ADFH Operation Manual User Manual

Page 14

Advertising
background image

Form O-ADF/RDF, P/N 148385R2, Page 14

3.0 Operation and Service (cont'd)

3.6 Gas Train Including Burner, Gas Controls, Manifold Arrangements, and Gas

Pressure Switches (cont'd)

FIGURE 27 -

Maxitrol Series

44 Components

used in

Recirculation

Air Gas Control

Option AG48

Amplifier, P/N 204450

Selector,

P/N 204451

Return Air Sensor,

P/N 204452

Outside Air Sensor,

P/N 204452

Discharge

Air Sensor,

P/N 204453

Service - ALL Gas Controls: Check all electrical connections. A qualified service person should refer to the control

manufacturer's literature for assistance in identifying problems and determining the correct solution. None of the controls

have field replaceable parts. All components must be replaced with identical replacement parts.

Option AG51 electronic

modulation system is

comprised of the same

Maxitrol Series 44 controls

as Option AG48 plus a

remote sensor/selector.

FIGURE 28 - Option

AG51 includes Maxitrol

Series 44 Components

used in AG48 plus a

Remote Sensor

Remote

Sensor/

Selector,

P/N 204456

Manifold Arrangements

Description: The manifold is the gas train from the gas supply connection to the

burner. The manifold selection ordered determines the manifold arrangement including

all of the gas train components except the main control valve. Manifold arrangements

are available for varying BTUH ranges and gas controls and meet ANSI, CSA, FM or

GAP (former IRI) requirements.
All manifold arrangements include two 5psi rated manual shutoffs.
These systems are designed to operate on a natural gas supply differential pressure

range of a minimum of 4.3-5.0" w.c. plus the manifold pressure drop. Maximum sup-

ply pressure depends on manifold selection; see below. If the gas supply pressure is

above the maximum allowed, it is necessary to install a field-supplied step-down gas

regulator in the supply line. Order and install the appropriate Gas Regulator Kit, Option

CZ1 (1") or CZ2 (1-1/2"). Follow the instructions provided with the kit. Measure the gas

pressure between the step-down regulator and the unit.

The table right lists the

minimum supply pressure

required for manifold and

gas control combinations.

Refer to the wiring diagram

to be sure which combina-

tion of options applies to the

system being serviced.

Minimum Supply Gas Pressure ("w.c.) for Full Fire

Manifold Option

BM75

BM76

BM78

BM79

BM80

BM81

with Gas Control

Option

AG1

AG3

AG 30, 31, 32, 33,

35, 36, 37, 47, 48,

or 51

AG 30, 31, 32, 33, 35, 36, 37, 47, 48, or 51

Manifold Size

1"

1"

1"

1"

1-1/4"

1-1/4"

2"

MBH

Nat

Pro

Nat

Pro

Nat

Pro

Nat

Pro

Nat

Pro

Nat

Pro

Nat

Pro

250

4.0

1.4

4.0

N/A

4.1

1.6

4.4

1.6

4.6

1.6

4.5

1.6

5.1

1.8

500

5.3

1.9

5.0

N/A

5.8

2.3

6.0

2.3

5.2

1.9

5.0

1.7

5.3

1.9

750

7.5

2.7

6.8

N/A

8.5

3.3

8.4

3.3

6.1

2.3

5.7

2.0

5.5

1.9

1000

12.4

4.7

11.7

4.6

7.4

2.8

6.7

2.4

5.8

2.1

1250

9.1

3.5

8.0

2.9

6.2

2.2

1500

11.2

4.3

9.6

3.5

6.6

2.4

1750

13.6

5.3

11.5

4.2

7.2

2.6

2000

16.5

6.3

13.7

5.0

7.8

2.8

2500

23.3

8.9

18.9

7.0

9.4

3.4

3000

11.3

4.1

Maximum Supply

Pressure by Manifold

If the gas train includes either or both high and low gas pressure switches, the switches

monitor gas pressure downstream from the safety valves.
If the gas pressure in a system equipped with a high gas pressure switch (standard

with manifold Options BM 78, 79, 80 and 81; Option BP2 with other manifolds) exceeds

the setpoint, the switch will open the electrical circuit to the burner, stopping all gas

flow. The high gas pressure switch is a manually reset device.
A low gas pressure switch (Option BP3) will shutoff the gas flow if the gas pressure

drops below the setpoint of the low pressure switch. The low gas pressure switch will

automatically reset when the gas pressure rises above the setpoint.

(Refer to the wiring diagram or rating

plate to identify the manifold on the

system being serviced.)

Manifold Option BM75, BM76 - 1/2 psi

Manifold Option BM78, BM79 - 2 psi

Manifold Option BM80, BM81 - 5 psi