0 operation and service (cont'd) – Reznor ADFH Operation Manual User Manual

Page 16

Advertising
background image

Form O-ADF/RDF, P/N 148385R2, Page 16

3.0 Operation

and Service

(cont'd)

Function: The potentiometer is a manually set switch

that operates either the discharge damper (Option

AR19) or the return air damper (Option AR22) provid-

ing a mixture of return and outside air. It is a remotely

located switch that requires manual adjustment.
Service: If the potentiometer does not function prop-

erly, replace it with an identical switch.

Description/Function: The pressure null switch is a diaphragm operated differential

pressure switch used in makeup air applications to automatically control building pres-

sure. It maintains a selected positive or negative pressure setpoint by changing the

amount of outside air being introduced to the building through modulating outside air

damper. As more pressure is required in the building, the pressure null switch activates

the damper motor driving the outside air damper towards the full open position (caus-

ing the bypass return air damper to go toward the closed position). Conversely, as less

pressure is required, the switch drives the outside air damper in the opposite direction.
Service: Clean the tubing and the screened ends of the pressure tap vents. Be sure

that the switch is installed with the diaphragm in a vertical plane and that the pressure

taps are sheltered from the wind. For further service, follow the manufacturer's instruc-

tions included with the switch.

Pressure Null Switch

(automatic building

pressure sensor)

FIGURE 31 -

Potentiometer,

P/N 16110

Potentiometer

FIGURE 33 -

Photohelic

Pressure Sensor,

P/N 159893

Photohelic Pressure

Switch

(automatic

building pressure

sensor)

Description/Function: The photohelic pressure switch is a phototransister relay oper-

ated positive pressure switch used in makeup air applications to automatically control

building pressure. It maintains a selected positive pressure setpoint by changing the

amount of outside air being introduced to the building through a modulating outside air

damper. As more pressure is required in the building, the switch activates the damper

motor driving the outside air damper towards the full open position (causing the bypass

return air damper to go toward the closed position). Conversely, as less pressure is

required, the switch drives the outside air damper in the opposite direction.
Service: Clean the tubing and the screened ends of the pressure tap vents.
If the interior of the switch is protected from dust, dirt, corrosive gases and fluids, years

of trouble-free service may be expected. Zero adjustment should be checked and reset

occasionally to maintain accuracy; follow the manufacturer's instructions included with

the switch.

There are no field-repairable parts in this switch. If the switch should require repair,

contact either the system or the switch manufacturer concerning switch replacement

or repair.

FIGURE 32 -

Pressure Null

Switch, P/N 88052

3.7 Inlet Air Controls

(cont'd)

3.8 Other Optional

Controls

Outside Air Cutoff Control (Option BN2)

Location: The control is in the electrical box (FIGURE 9.); the sensor is in the air inlet.

Function: After sensing pilot flame, the burner ignites at its lowest input rate. The

"amount of heat" required to reach the desired discharge temperature also depends

on the temperature of the incoming outside air. The outside air control is factory set at

60°F (adjustable 25-250°F). The burner reacts differently depending on the entering air

temperature and the setting on the outside air control. The burner --

• may not ignite (pilot valve will not open);

If the actual temperature of the outside air is above the setpoint on the outside air

control, the burner will not ignite.

• may modulate to satisfy discharge setting;

• would shutdown completely only on Option BN2 control, once burner has been fired;

or

Modulating operation will depend on the temperature rise between the outside air

and the discharge air setting.

• may remain on continuous low fire.

If the outside air control is set too high, the burner will continuously burn on low fire

as long as the control switch is set to "winter".

When the outside air control is set properly for the climate, the system blower will con-

tinue to provide the required makeup air (ventilation) at the ambient outdoor tempera-

ture (burner not operating) even when the control switch is set to "winter".
Service: If the control does not function properly, replace it with an identical switch.

FIGURE 34 -

Outside Air Cutoff

Control, P/N 126170

Advertising
This manual is related to the following products: