Page 13

Advertising
background image

DSE Model 3000 Series Control & Instrumentation System Operators Manual

Part No. 057-086 3000 Series OPERATING MANUAL ISSUE 4 03/12/2009 ADM

13

4.2 TERMINAL DESCRIPTION

4.2.1 DC SUPPLY, FUEL AND START OUTPUTS

PIN

No

DESCRIPTION

CABLE

SIZE

NOTES

1

DC Plant Supply Input
(Negative)

2.5mm²

AWG 13

2

DC Plant Supply Input
(Positive)

2.5 mm²

AWG 13

(Recommended Maximum Fuse 15A anti-surge)
Supplies the module (2A anti-surge requirement) and all
output relays

3

Output A (FUEL)

1.0mm²

AWG 18

Plant Supply Positive from terminal 2. 3 Amp rated.

4

Output B (START)

1.0mm²

AWG 18

Plant Supply Positive from terminal 2. 3 Amp rated.

5

Output C

1.0mm²

AWG 18

Plant Supply Positive from terminal 2. 3 Amp rated.

6

Output D

1.0mm²

AWG 18

Plant Supply Positive from terminal 2. 3 Amp rated.

7

Charge fail / excite

2.5mm²

AWG 13

Do not connect to ground (battery negative).
If charge alternator is not fitted, leave this terminal
disconnected.


4.2.2 GENERATOR VOLTAGE SENSING AND DIGITAL INPUTS

PIN

No

DESCRIPTION

CABLE

SIZE

NOTES

8

Generator Neutral (N) input

1.0mm²

AWG 18

Connect to generator Neutral terminal (AC)

9

Generator L1 (U) voltage
monitoring

1.0mm²

AWG 18

Connect to generator L1 (U) output (AC)
(Recommend 2A fuse)

4.2.3 MAGNETIC PICKUP AND DIGITAL INPUTS (MODEL 3110-XX-01)


Model 3110-xx-01 (Magnetic pickup enabled module)

NOTE:- CAN interface is not fitted to the 3110-xx-01 module

PIN

No

DESCRIPTION

CABLE

SIZE

NOTES

10

Magnetic pickup Positive

0.5mm²

AWG 20

Connect to Magnetic Pickup device

11

Magnetic pickup Negative

0.5mm²

AWG 20

Connect to Magnetic Pickup device

12

Configurable digital input A

0.5mm²

AWG 20

Switch to negative

13

Configurable digital input B

0.5mm²

AWG 20

Switch to negative

14

Configurable digital input C

0.5mm²

AWG 20

Switch to negative

15

Configurable digital input D

0.5mm²

AWG 20

Switch to negative

16

Configurable digital input E

0.5mm²

AWG 20

Switch to negative

17

Configurable digital input F

0.5mm²

AWG 20

Switch to negative


NOTE:- Screened cable must be used for connecting the Magnetic Pickup, ensuring that the screen is

earthed at one end ONLY.