6.2.3 ENGINE RUNNING


In manual mode, the load is not transferred to the generator unless a ‘loading request’ is made.
A loading request can come from a number of sources.

Activation of an auxiliary input that has been configured to remote start on load

Activation of the inbuilt exercise scheduler if configured for ‘on load’ runs.

NOTE:-The load transfer signal remains inactive until the Oil Pressure has risen. This prevents

excessive wear on the engine.


Once the load has been transferred to the generator, it will not be automatically removed. To manually transfer the
load back to the mains either:

Press the auto mode

button to return to automatic mode. The set will observe all auto mode start

requests and stopping timers before beginning the Auto mode stopping sequence.

Press the stop button

De-activation of an auxiliary input that has been configured to remote start on load

6.2.4 STOPPING SEQUENCE


In manual mode the set will continue to run until either :

The stop button

is pressed – The set will immediately stop

The auto button

is pressed. The set will observe all auto mode start requests and stopping timers