Symptom possible remedy – Winco DSE3000 Series User Manual

Page 36

Advertising
background image

DSE Model 3000 Series Control and Instrumentation System Operators Manual

36

Part No. 057-086 3000 Series OPERATING MANUAL ISSUE 4 03/12/2009 ADM

SYMPTOM

POSSIBLE REMEDY

Incorrect reading on Engine
gauges

Fail to stop alarm when engine is
at rest

Check engine is operating correctly. Check sensor and wiring.

Module appears to ‘revert’ to an
earlier configuration

When editing a configuration using the PC software it is vital that the
configuration is first ‘read’ from the controller before editing it. This edited
configuration must then be “written” back to the controller for the changes to
take effect.

When editing a configuration using the Front Panel Editor, be sure to press the

Save

button to save the change before moving to another item or exiting

the Front Panel Editor.

Set will not take load

Ensure the generator is available.

Check that the output configuration is correct to drive the load switch device
and that all connections are correct.

Remember that the set will not take load in manual mode unless a remote start
on load input is present.

Inaccurate generator
measurements on controller
display

The 3000 series controller is true RMS measuring so gives more accurate
display when compared with an ‘average’ meter such as an analogue panel
meter or some lower specified digital multimeters.

Accuracy of the controller is better than 1% of full scale. Ie Gen volts full scale
is 333V ph-n so accuracy is ±3.33V (1% of 333V).


NOTE:- The above fault finding is provided as a guide check-list only. As the module can be

configured to provide a wide range of different features, always refer to the source of your module
configuration if in doubt.




Advertising