DSE Model 3000 Series Control and Instrumentation System Operators Manual

32

Part No. 057-086 3000 Series OPERATING MANUAL ISSUE 4 03/12/2009 ADM

Parameters with multiple choices use the following identification tables for the parameter values.

INPUT SOURCE LIST

0

User Configured

1

RESERVED

Alarm Mute

2

RESERVED

Alarm Reset

3

Alternative configuration

4

Coolant Temperature Switch

5

Emergency Stop

6

External Panel Lock

7

RESERVED

Generator Closed Auxiliary

8

RESERVED

Lamp Test

9

Low Fuel Level Switch

10

Oil Pressure Switch

11

Remote

Start Off Load

12

Remote Start On Load

13

Smoke Limiting

INPUT ACTION LIST

INPUT ARMING LIST

Index

Action

Index

Arming

0

Electrical Trip

0

Always

1

Shutdown

1

From Safety On

2

Warning

2

From Starting

3

Never

INPUT POLARITY LIST

Index

Action

OUTPUT POLARITY LIST

0

Close to Activate

Index

Arming

1

Open to Activate

0

Energise

1

De-energise

CAN DATA FAIL ACTION

Index

Action

CAN DATA FAIL ARMING

0

None

Index

Arming

1

Shutdown

0

From Safety On

2

Warning always latched

1

From Starting

AC SYSTEM

Index

AC System

Instrumentation

0

Single phase 2 wire

L-N

1

2 phase, 3 wire (L12/L13)

L-N x 2

2

3 phase, 4 wire

L-N x sqrt(3)

3

3 phase, 3 wire delta

L-N

4

3 phase, 4 wire delta

L-N x 2