4 inputs, 5 outputs – Winco DSE3000 Series User Manual

Page 8

Advertising
background image

DSE Model 3000 Series Control and Instrumentation System Operators Manual

8

Part No. 057-086 3000 Series OPERATING MANUAL ISSUE 4 03/12/2009 ADM

3.4 INPUTS

3.4.1 DIGITAL INPUTS


Number

6

Arrangement

Contact between terminal and ground

Low level threshold

40% of DC supply voltage

High level threshold

60% of DC supply voltage

Maximum input voltage

DC supply voltage positive terminal

Minimum input voltage

DC supply voltage negative terminal

Contact wetting current

2.5mA @12V typical
5mA @ 24V typical

Open circuit voltage

Plant supply


3.4.2 CHARGE FAIL INPUT


Minimum voltage

0V

Maximum voltage

35V (plant supply)

Resolution

0.2V

Accuracy

± 1% of max measured voltage

Excitation

Active circuit constant power output

Output Power

2.5W Nominal @12V and 24V

Current at 12V

210mA

Current at 24V

105mA

3.4.3 MAGNETIC PICKUP


Type

Single ended input, capacitive coupled

Minimum voltage

0.5V RMS

Max common mode
voltage

±2V

Maximum voltage

Clamped to ±70V by transient suppressers, dissipation not to exceed 1W.

Maximum frequency

10,000Hz

Resolution

6.25 RPM

Accuracy

±25 RPM

Flywheel teeth

10 to 500


3.5 OUTPUTS

3.5.1 OUTPUTS A & B (FUEL AND START)


Type

Fuel (A) and Start (B) outputs. Supplied from DC supply terminal 2.
Fully configurable when CAN engine is selected.

Rating

2A @ 35V

Protection

Protected against over current & over temperature. Built in load dump feature.

3.5.2 CONFIGURABLE OUTPUTS C & D


Type

Fully configurable, supplied from DC supply terminal 2.

Rating

2A @ 35V

Protection

Protected against over current & over temperature. Built in load dump feature.

Advertising