5 pc configuration interface connector – Winco DSE3000 Series User Manual

Page 14

Advertising
background image

DSE Model 3000 Series Control and Instrumentation System Operators Manual

14

Part No. 057-086 3000 Series OPERATING MANUAL ISSUE 4 03/12/2009 ADM

4.2.4 CAN AND DIGITAL INPUTS (MODEL 3110-XX-02)


Model 3110-xx-020 (Can enabled module) only.

NOTE:- Magnetic Pickup interface is not fitted to the 3110-xx-02 module

PIN

No

DESCRIPTION

CABLE

SIZE

NOTES

10

CAN port L

0.5mm²

AWG 20

Use only 120

CAN approved cable

11

CAN port H

0.5mm²

AWG 20

Use only 120

CAN approved cable

12

Configurable digital input A

0.5mm²

AWG 20

Switch to negative

13

Configurable digital input B

0.5mm²

AWG 20

Switch to negative

14

Configurable digital input C

0.5mm²

AWG 20

Switch to negative

15

Configurable digital input D

0.5mm²

AWG 20

Switch to negative

16

Configurable digital input E

0.5mm²

AWG 20

Switch to negative

17

Configurable digital input F

0.5mm²

AWG 20

Switch to negative


NOTE:- Screened 120

impedance cable specified for use with CAN must be used for the CAN link and

the Multiset comms link.
DSE stock and supply Belden cable 9841 which is a high quality 120

impedance cable suitable for CAN

use (DSE part number 016-030)



4.2.5 PC CONFIGURATION INTERFACE CONNECTOR

DESCRIPTION

CABLE

SIZE

NOTES

Socket for connection to PC with DSE
Configuration Suite PC software.

0.5mm²

AWG 20

This is a standard USB type A to

type B cable.

NOTE:- The USB connection cable between the PC and the 3000 series module must not be extended

beyond 5m (5yds). For distances over 5m, it is possible to use a third party USB extender. Typically, they
extend USB up to 50m (yds). The supply and support of this type of equipment is outside the scope of
Deep Sea Electronics PLC.

CAUTION!: Care must be taken not to overload the PCs USB system by connecting more than the

recommended number of USB devices to the PC. For further information, consult your PC supplier.

CAUTION!: This socket must not be used for any other purpose.


This configuration cable is
the same as normally used
between a PC and a USB
printer.

Advertising