7 fault icons – Winco DSE3000 Series User Manual

Page 26

Advertising
background image

DSE Model 3000 Series Control and Instrumentation System Operators Manual

26

Part No. 057-086 3000 Series OPERATING MANUAL ISSUE 4 03/12/2009 ADM

8.7 FAULT ICONS

ICON

DESCRIPTION

AUXILIARY INPUTS

Auxiliary inputs can be user configured and will display the message as written by
the user.

FAIL TO START

The engine has not fired after the preset number of start attempts

FAIL TO STOP

The module has detected a condition that indicates that the engine is running when
it has been instructed to stop.

NOTE:

NOTE:

NOTE:

NOTE:---- ‘Fail to Stop’ could indicate a faulty oil pressure sensor

‘Fail to Stop’ could indicate a faulty oil pressure sensor

‘Fail to Stop’ could indicate a faulty oil pressure sensor

‘Fail to Stop’ could indicate a faulty oil pressure sensor ---- If

If

If

If

engine is at rest check oil sensor wiring and configuration.

engine is at rest check oil sensor wiring and configuration.

engine is at rest check oil sensor wiring and configuration.

engine is at rest check oil sensor wiring and configuration.

LOW OIL PRESSURE

The module detects that the engine oil pressure has fallen below the low oil
pressure pre-alarm setting level after the Safety On timer has expired.

ENGINE HIGH
TEMPERATURE

The module detects that the engine coolant temperature has exceeded the high
engine temperature pre-alarm setting level after the Safety On timer has expired.

UNDERSPEED

The engine speed has fallen below the underspeed pre alarm setting

OVERSPEED

The engine speed has risen above the overspeed pre alarm setting

CHARGE FAILURE

The auxiliary charge alternator voltage is low as measured from the W/L terminal.

LOW FUEL LEVEL

The level detected by the fuel level sensor is below the low fuel level setting.

BATTERY UNDER
VOLTAGE / BATTERY
OVER VOLTAGE

The DC supply has fallen below or risen above the low/high volts setting level.

GENERATOR UNDER
VOLTAGE

The generator output voltage has fallen below the pre-set pre-alarm setting after
the Safety On timer has expired.

GENERATOR OVER
VOLTAGE

The generator output voltage has risen above the pre-set pre-alarm setting.

GENERATOR UNDER
FREQUENCY

The generator output frequency has fallen below the pre-set pre-alarm setting after
the Safety On timer has expired.

GENERATOR OVER
FREQUENCY

The generator output frequency has risen above the pre-set pre-alarm setting.

CAN ECU WARNING
CAN ECU SHUTDOWN

The engine ECU has detected an alarm – CHECK ENGINE LIGHT
Contact Engine Manufacturer for support.

CAN DATA FAIL

The module is configured for CAN operation and does not detect data on the
engine Can datalink.

EMERGENCY STOP

The emergency stop button has been depressed. This a failsafe (normally closed
to battery positive) input and will immediately stop the set should the signal be
removed.
Removal of the battery positive supply from the emergency stop input will also
remove DC supply from the Fuel and Start outputs of the controller.

NOTE:- The Emergency Stop Positive signal must be present otherwise

the unit will shutdown.

MAGNETIC PICKUP
FAILURE

Pulses are no longer being detected from the magnetic pickup probe (3110-xxx-01
magnetic pickup version only)

INTERNAL MEMORY
ERROR

Either the configuration file or engine file memory is corrupted. Contact your
supplier for assistance.

Advertising