Chapter 4 Parameters|
4-84
Revision August 2008, 03VE, SW V2.04
Settings
Functions
Descriptions
19
Pulse frequency
command
Max. frequency Pr.01-00 is regarded as 100%.
03-19
Analog Output Gain 1
Unit: 0.1
03-22
Analog Output Gain 2 (need to be used with EMV-APP01)
Unit: 0.1
03-25
Analog Output Gain 3 (need to be used with EMV-APP01)
Unit: 0.1
Control
mode
VF VFPG SVC
FOCPG TQRPG
Factory setting: 100.0
Settings
0 to 200.0%
It is used to adjust the analog voltage level that terminal AFM outputs.
This parameter is set the corresponding voltage of the analog output 0.
03-20
Analog Output Value in REV Direction 1
03-23
Analog Output Value in REV Direction 2
03-26
Analog Output Value in REV Direction 3
Control
mode
VF VFPG SVC
FOCPG TQRPG
Factory setting: 0
Settings
0
Absolute value in REV direction
1
Output 0V in REV direction
2
Enable output voltage in REV direction
03-18
03-21
03-24
03-20=0
03-23=0
03-26=0
03-20=1
03-23=1
03-26=1
10V( 20mA)
03-20=2
03-23=2
03-26=2
5V
( 12mA)
10V( 20mA)
0V
( 0mA)
10V( 20mA)
0V
( 0mA)
F requenc y
F requenc y
Selections for the analog output dir ec ti on