Delta Electronics AC Motor Drive VFD-VE Series User Manual

Page 83

Advertising
background image

Chapter 4 Parameters|

4-34

Revision August 2008, 03VE, SW V2.04

Pr.

Explanation

Settings

Factory

Setting

VF VFPG SVC FOCPG TQRPG

39: Ground current detection error (Hd3)

○

○

○

○

○

40: Auto tuning error (AuE)

○

○

○

41: PID feedback loss (AFE)

○

○

○

○

○

42: PG feedback error (PGF1)

○

○

○

43: PG feedback loss (PGF2)

○

○

○

44: PG feedback stall (PGF3)

○

○

45: PG slip error (PGF4)

○

○

46: PG ref input error (PGr1)

○

○

○

○

○

47: PG ref loss (PGr2)

○

○

○

○

○

48: Analog current input loss (ACE)

○

○

○

○

○

49: External fault input (EF)

○

○

○

○

○

50: Emergency stop (EF1)

○

○

○

○

○

51: External Base Block (B.B.)

○

○

○

○

○

52: Password error (PcodE)

○

○

○

○

○

53:

Reserved

○

○

○

○

○

54: Communication error (cE1)

○

○

○

○

○

55: Communication error (cE2)

○

○

○

○

○

56: Communication error (cE3)

○

○

○

○

○

57: Communication error (cE4)

○

○

○

○

○

58: Communication Time-out (cE10)

○

○

○

○

○

59: PU time-out (cP10)

○

○

○

○

○

60: Brake transistor error (bF)

○

○

○

○

○

61: Y-connection/

Δ-connection switch error (ydc)

○

○

○

○

62: Decel. Energy Backup Error (dEb)

○

○

○

○

○

63: Slip error (oSL)

○

○

○

○

64: Broken belt error (bEb)

○

○

○

○

○

65: Error PID feedback signal of tension (tdEv)

○

○

○

○

○

06-32

Output Frequency for
Malfunction

0.00~655.35 Hz

0.00

○

○

○

○

○

06-33

Output AC Voltage for
Malfunction

0.0~6553.5 V

0.0

○

○

○

○

○

06-34

DC Voltage for
Malfunction

0.0~6553.5 V

0.0

○

○

○

○

○

06-35

Current Value for
Malfunction

0.00~655.35 Amp

0.00

○

○

○

○

○

06-36

IGBT Temperature for
Malfunction

0.0~6553.5 °C

0.0

○

○

○

○

○



Group 8 High-function PID Parameters
New parameters 08-21~08-99

Pr.

Explanation

Settings

Factory

Setting

VF VFPG SVC FOCPG TQRPG

08-00

Input Terminal for PID
Feedback

0: No function
1: Negative PID feedback from external terminal AVI
(Pr.03-00)
2: Negative PID feedback from PG card (Pr.10-15,
skip direction)
3: Negative PID feedback from PG card (Pr.10-15)

4: Positive PID feedback from external terminal AVI
(Pr.03-00)
5: Positive PID feedback from PG card (Pr.10-15,
skip direction)
6: Positive PID feedback from PG card (Pr.10-15)

0

○

○

○

○

08-01

Proportional Gain (P)

0.0~500.0%

80.0

○

○

○

○

0: Disable

0

○

○

○

○

08-21

Tension Control
Selection

1: Closed-loop, speed mode

○

○

○

○

2: Line speed, speed mode

○

○

○

○

3: Reserved

4: Open-loop, torque mode

○

Advertising