Delta Electronics AC Motor Drive VFD-VE Series User Manual
Page 177

Chapter 4 Parameters|
4-128
Revision August 2008, 03VE, SW V2.04
Control
mode
VF VFPG SVC
FOCPG TQRPG
Factory Setting: 50.0
Settings 0.0
to
1000.0
08-30
Tension PID I1
Unit: 0.01
Control
mode
VF VFPG SVC
FOCPG TQRPG
Factory Setting: 1.00
Settings
0.00 to 500.00 sec
08-31
Reserved
08-32
Tension PID P2
Unit: 0.1
Control
mode
VF VFPG SVC
FOCPG TQRPG
Factory Setting: 50.0
Settings 0.0
to
1000.0
08-33
Tension PID I2
Unit: 0.01
Control
mode
VF VFPG SVC
FOCPG TQRPG
Factory Setting: 1.00
Settings
0.00 to 500.00 sec
08-34
Reserved
08-35
PID Output Status
Control
mode
VF VFPG SVC
FOCPG TQRPG
Factory Setting: 0
Settings
0
Positive
output
1
Negative
output
08-36
Tension/Line Speed PID Output Limit
Unit: 0.01
Control
mode
VF VFPG SVC
FOCPG TQRPG
Factory Setting: 20.00
Settings
0 to 100.00% (according to Pr.01-00)
08-37
Source of Line Speed Input Command
Control
mode
VF VFPG SVC
FOCPG TQRPG
Factory Setting: 0
Settings
0
Disable
1
Analog input (Pr. 03-00~03-02 is set to 12 line speed)
2
RS-485 communication setting (Pr.08-41)