Chapter 4 Parameters|

4-102

Revision August 2008, 03VE, SW V2.04

Control Mode

Settings

VF

VFPG

SVC

FOCPG TQRPG

52: Password error (PcodE)

○

○

○

○

○

53:

Reserved

54: Communication error (cE1)

○

○

○

○

○

55: Communication error (cE2)

○

○

○

○

○

56: Communication error (cE3)

○

○

○

○

○

57: Communication error (cE4)

○

○

○

○

○

58: Communication Time-out (cE10)

○

○

○

○

○

59: PU time-out (cP10)

○

○

○

○

○

60: Brake transistor error (bF)

○

○

○

○

○

61: Y-connection/

Δ

-connection switch error (ydc)

○

○

○

○

62: Decel. Energy Backup Error (dEb)

○

○

○

○

○

63: Slip error (oSL)

○

○

○

○

64: Broken belt error (bEb)

○

○

○

○

○

65: Error PID feedback signal of tension (tdEv)

○

○

○

○

○

It will record when the fault occurs and force stopping. For the Lv, it will record when it is

operation, or it will warn without record.

Setting 62: when DEB function is enabled, the drive will execute DEB and record to the Pr.06-

17 to Pr.06-22 simultaneously.

06-23

Fault Output Option 1

Unit: 1

06-24

Fault Output Option 2

Unit: 1

06-25

Fault Output Option 3

Unit: 1

06-26

Fault Output Option 4

Unit: 1

Control

mode

VF VFPG SVC

FOCPG TQRPG

Factory Setting: 0

Settings

0 to 65535 sec (refer to bit table for fault code)

These parameters can be used with multi-function output (set Pr.02-11 to Pr.02-14 to 35-38)

for the specific requirement. When the fault occurs, the corresponding terminals will be

activated (It needs to convert binary value to decimal value to fill in Pr.06-23 to Pr.06-26).

Bit0

Bit1

Bit2

Bit3

Bit4

Bit5

Bit6

Fault code

current Volt.

OL

SYS

FBK

EXI

CE

0: No fault

1: Over-current during acceleration
(ocA)

●

2: Over-current during deceleration
(ocd)

●

3: Over-current during constant
speed (ocn)

●