Group 5 motor parameters – Delta Electronics AC Motor Drive VFD-VE Series User Manual

Page 82

Advertising
background image

Chapter 4 Parameters|

Revision August 2008, 03VE, SW V2.04

4-33


Group 5 Motor Parameters

Pr.

Explanation

Settings

Factory

Setting

VF VFPG SVC FOCPG TQRPG

05-00

Motor Auto Tuning

0: No function
1: Rolling test
2: Static Test
3: Reserved

0

○

○

○

05-01

Full-load Current of
Motor 1

40-100% #.##

○

○

○

○

○

05-02

Rated power of Motor 1

0~655.35

#.##

○

○

○

05-03

Rated speed of Motor 1
(rpm)

0~65535
1710 (60Hz, 4 poles), 1410 (50Hz, 4 poles)

1710

○

○

○

○


Group 6 Protection Parameters
New setting 0 for Pr.06-01, new settings 64~65 for Pr.06-17~Pr.06-22 and new parameters 06-

32~06-36.

Pr.

Explanation

Settings

Factory

Setting

VF VFPG SVC FOCPG TQRPG

0.0: Disable

350.0~450.0Vdc 380.0

○

○

○

○

○

06-01

Over-voltage Stall
Prevention

700.0~900.0Vdc 760.0

○

○

○

○

○

06-17

Present Fault Record

0: No fault

0

○

○

○

○

○

1: Over-current during acceleration (ocA)

○

○

○

○

○

2: Over-current during deceleration (ocd)

0

○

○

○

○

○

06-18

Second Most Recent
Fault Record

3: Over-current during constant speed (ocn)

○

○

○

○

○

4: Ground fault (GFF)

○

○

○

○

○

5: IGBT short-circuit (occ)

0

○

○

○

○

○

06-19

Third Most Recent Fault
Record

6: Over-curent at stop (ocS)

○

○

○

○

○

7: Over-voltage during acceleration (ovA)

○

○

○

○

○

8: Over-voltage during deceleration (ovd)

0

○

○

○

○

○

06-20

Fourth Most Recent
Fault Record

9: Over-voltage during constant speed (ovn)

○

○

○

○

○

10: Over-voltage at stop (ovS)

○

○

○

○

○

11: Low-voltage during acceleration (LvA)

○

○

○

○

○

12: Low-voltage during deceleration (Lvd)

○

○

○

○

○

06-21

Fifth Most Recent Fault
Record

13: Low-voltage during constant speed (Lvn)

○

○

○

○

○

14: Low-voltage at stop (LvS)

0

○

○

○

○

○

15: Phase loss (PHL)

○

○

○

○

○

16: IGBT heat sink over-heat (oH1)

○

○

○

○

○

17: Heat sink over-heat (oH2)(for 40HP above)

0

○

○

○

○

○

06-22

Sixth Most Recent Fault
Record

18: TH1 open loop error (tH1o)

○

○

○

○

○

19: TH2 open loop error (tH2o)

○

○

○

○

○

20: Fan error signal output

○

○

○

○

○

21: over-load (oL) (150% 1Min)

○

○

○

○

○

22: Motor 1 over-load (EoL1)

○

○

○

○

○

23: Motor 2 over-load (EoL2)

○

○

○

○

○

24: Motor PTC overheat (oH3)

○

○

○

○

○

25: Fuse error (FuSE)

○

○

○

○

○

26: over-torque 1 (ot1)

○

○

○

○

○

27: over-torque 1 (ot2)

○

○

○

○

○

28: Reserved

○

○

○

○

○

29:

Reserved

○

○

○

○

○

30: Memory write-in error (cF1)

○

○

○

○

○

31: Memory read-out error (cF2)

○

○

○

○

○

32: Isum current detection error (cd0)

○

○

○

○

○

33: U-phase current detection error (cd1)

○

○

○

○

○

34: V-phase current detection error (cd2)

○

○

○

○

○

35: W-phase current detection error (cd3)

○

○

○

○

○

36: Clamp current detection error (Hd0)

○

○

○

○

○

37: Over-current detection error (Hd1)

○

○

○

○

○

38: Over-voltage detection error (Hd2)

○

○

○

○

○

Advertising