Delta Electronics AC Motor Drive VFD-VE Series User Manual
Page 155

Chapter 4 Parameters|
4-106
Revision August 2008, 03VE, SW V2.04
Settings
0.0
to
100.0%
It is used to set the PTC level, and the corresponding value for 100% is max. analog input
value.
06-31
Filter Time for PTC Detection
Unit: 0.01
Control
mode
VF VFPG SVC
FOCPG TQRPG
Factory Setting: 0.20
Settings
0.00 to 10.00 sec
06-32
Output Frequency for Malfunction
Unit: 0.01
Control
mode
VF VFPG SVC
FOCPG TQRPG
Factory Setting: 0.00
Settings
0.00 to 655.35 Hz
06-33
Output AC Voltage for Malfunction
Unit: 0.1
Control
mode
VF VFPG SVC
FOCPG TQRPG
Factory Setting: 0.0
Settings
0.0~6553.5
V
06-34
DC Voltage for Malfunction
Unit: 0.1
Control
mode
VF VFPG SVC
FOCPG TQRPG
Factory Setting: 0.0
Settings
0.0~6553.5
V
06-35
Current Value for Malfunction
Unit: 0.01
Control
mode
VF VFPG SVC
FOCPG TQRPG
Factory Setting: 0.00
Settings
0.00~655.35
Amp
06-36
IGBT Temperature for Malfunction
Unit: 0.1
Control
mode
VF VFPG SVC
FOCPG TQRPG
Factory Setting: 0.0
Settings
0.0~6553.5
°C