Delta Electronics AC Motor Drive VFD-VE Series User Manual
Page 201

Chapter 4 Parameters|
4-152
Revision August 2008, 03VE, SW V2.04
When integral time is set to 0, it is disabled. Pr.10-08 defines the switch frequency for the
ASR1 (Pr.10-04, Pr.10-05) and ASR2 (Pr.10-06, Pr.10-07).
10-08
10-04
10-05
10-06
10-07
Hz
PI
10-21
10-22
0Hz
5Hz
5Hz
When using multi-function input terminals to switch ASR1/ASR2, the diagram will be shown as
follows.
ON
OFF
ASR 1
0.1 sec
OFF
0.1 sec
ASR 1
ASR 2
Setting multi-function input terminal to 27
(ASR1/ASR2 switch)
10-09
ASR Primary Low Pass Filter Gain
Unit: 0.001
Control
mode
FOCPG
Factory Setting: 0.008
Settings
0.000 to 0.350 sec
It defines the filter time of the ASR command.
10-10
PG Stall Level
Unit: 1
Control
mode
VFPG
FOCPG
Factory Setting: 115
Settings
0 to 120% (0: disable)
This parameter determines the maximum PG feedback signal allowed before a fault occurs.
(max. output frequency Pr.01-00 =100%)
10-11
PG Stall Detection Time
Unit: 0.1
Control
mode
VFPG
FOCPG
Factory Setting: 0.1
Settings
0.0 to 2.0 sec
10-12
PG Slip Range
Unit: 1
Control
mode
VFPG
FOCPG
Factory Setting: 50