LON 100 Internet Server Programmer’s Reference

Identifier Notes

PR_10

HVAC Critical Equipment RTN, Fire RTN (Display)

PR_16

HVAC RTN (lowest priority)

PR_NUL

Value not available

7.2.1.2.2 Comparison Functions

Table 24 describes the comparison functions an Alarm Generator can use when comparing
the values of the input and compare data points. You can select a comparison function for the

Alarm Generator by filling in the <UCPTcompFunction> property. When doing so, you must

reference each comparison function with the identifier strings listed in Table 24.

Table 24 Comparison Functions

Identifier Description

FN_GT

Greater than. In this case, an alarm will be generated if the input value is

greater than the compare value.

FN_LT

Less than. In this case, an alarm will be generated if the input value is less

than the compare value.

FN_GE

Greater than or equal. In this case, an alarm will be generated if the input

value is greater than or equal to the compare value.

FN_LE

Less than or equal. In this case, an alarm will be generated if the input value

is less than or equal to the compare value.

FN_EQ

Equal. In this case, an alarm will be generated if the input value is equal to

the compare value.

FN_NE

Not equal. In this case, an alarm will be generated if the input value is not

equal to the compare value.

FN_LIMIT

Compare against the limits defined by the high and low limit offset fields.

For more information on how these limits are used, see Hysteresis Levels and
Offset Limits
on page 7-13.


Different comparison functions should be used for different data point types, depending on
the <UCPTbaseType> of the data point. Table 25 lists the different data point base types,

and the comparison functions you can use with them.

Table 25 Base Types and Comparison Functions

Base Type

Valid <UCPTcompFunction>

BT_UNKNOWN, BT_ENUM, BT_ARRAY,

BT_STRUCT, BT_UNION, BT_BITFIELD

FN_EQ, FN_NE

BT_SIGNED_CHAR, BT_UNSIGNED_CHAR,

BT_SIGNED_SHORT, BT_UNSIGNED_SHORT,

BT_SIGNED_LONG, BT_UNSIGNED_LONG,
BT_FLOAT, BT_SIGNED_QUAD,

BT_UNSIGNED_QUAD, BT_DOUBLE

FN_GT, FN_LT, FN_GE,

FN_LE, FN_EQ, FN_NE,

FN_LIMIT