Alarmnotifierget, Alarmnotifierget -6, 2 alarmnotifierget – Echelon i.LON 100 e2 Internet Server User Manual
Page 112

8.2.1.2 AlarmNotifierGet
You can use the AlarmNotifierGet function to return the configuration of any Alarm Notifier
that you have added to the
i.
LON 100. You must reference the Alarm Notifier whose
configuration is to be returned by its index number in the <Data> parameter you supply to
the function, as in the example below.
<Data>
Parameter
<Data>
<iLONAlarmNotifier>
<Alarm>
<UCPTindex>0</UCPTindex>
</Alarm>
</iLONAlarmNotifier>
</Data>
<Result>
Parameter
<Result>
<iLONAlarmNotifier>
<Alarm>
<UCPTindex>0</UCPTindex>
<UCPTlastUpdate>2002-06-21T07:59:23Z
lastUpdate>
</UCPT
<UCPTdescription>Temperature Sensor Device</UCPTdescription>
<UCPTfbName>Alarm Notifier- 0</UCPTfbName>
<SCPTdelayTime>0.0</SCPTdelayTime>
<UCPTsumLogSize>100</UCPTsumLogSize>
<UCPThistLogSiz
100
UCPThistLogSize>
e>
</
<UCPTlogFormat>LF_TEXT</UCPTlogFormat>
<UCPTemailAggregTime>10</UCPTemailAggregTime>
<Point>
<UCPTindex>0</UCPTindex>
<UCPTpointName>NVL_AlarmGenIn1</UCPTpointName>
<UCPTalarmFlags>0 1 0 0 0 0 0</UCPTalarmFlags>
<UCPTalarmGroup>0</UCPTalarmGroup>
<UCPTpriority>1</UCPTpriority>
<UCPTdescription></UCPTdescription>
</Point>
<Mail>
<UCPTindex>0</UCPTindex>
<UCPTemailNickName>Joerg</UCPTemailNickName>
<UCPTemailAddress>js@nova</UCPTemailAddress>
</U
<UCPTemailSubject>Alarm Nofifier1: %ad</UCPTemailSubject>
<UCPTemailFormat>occured%dy/%dm/%dd
CPTemailFormat>
<UCPTemailAttachment>/root/Data/log1.csv</UCPTemailAttachment>
</Mail>
<ActiveAlarm>
<UCPTindex>0</UCPTindex>
<UCPTlevel>1</UCPTlevel>
<UCPTalarmText>Alarm (Binary)</UCPTalarmText>
<UCPTactAlarmType>AL_ALM_CONDITION</UCPTactAlarmType>
</ActiveAlarm>
<ActiveAlarm>
<UCPTindex>1</UCPTindex>
<UCPTlevel>2</UCPTlevel>
<UCPTalarmText>Alarm (Binary) offline</UCPTalarmText>
<UCPTactAlarmType>AL_OFFLINE</UCPTactAlarmType>
</ActiveAlarm>
<PassiveAlarm>
<UCPTindex>0</UCPTindex>
<UCPTlevel>255</UCPTlevel>
<UCPTalarmText>Normal Condition</UCPTalarmText>
i.
LON 100 Internet Server Program
8-6
mer’s Reference