Alarmgeneratorlist, Alarmgeneratorlist -4, 1 alarmgeneratorlist – Echelon i.LON 100 e2 Internet Server User Manual
Page 93

7.2.1.1 AlarmGeneratorList
Use the AlarmGeneratorList function to retrieve a list of the Alarm Generators that you
have added to the
i.
LON 100. The AlarmGeneratorList function takes an empty string as its
<Data> parameter, as in the example below.
The function returns the major and minor version numbers of the firmware implementation
that the Alarm Generator application is using in the <Result> parameter. The <Result>
parameter also includes an <Alarm> element for each Alarm Generator that you have added
to the
i.
LON 100. The next section, AlarmGeneratorGet, describes the properties included in
each <Alarm> element.
You could use the list of <Alarm> elements returned by this function as input for the
AlarmGeneratorGet function. The AlarmGeneratorGet function would then return the
configuration of every Alarm Generator included in the list.
<Data>
Parameter
Empty String
<Result>
Parameter
<Result>
<iLONAlarmGenerator>
<SCPTobjMajVer>1</SCPTobjMajVer>
<SCPTobjMinVer>1</SCPTobjMinVer>
<Alarm>
<UCPTindex>0</UCPTindex>
<UCPTdescription>Light Control</UCPTdescription>
<UCPTfbName>Alarm Generator- 0</UCPTfbName>
<UCPTlastUpdate>2002-06-20T12:37:05Z</UCPTlastUpdate>
</Alarm>
<Alarm>
<UCPTindex>1</UCPTindex>
<UCPTdescription> Heating Control </UCPTdescription>
<UCPTfbName>
Alarm Generator- 1</UCPTfbName>
<UCPTlastUpdate>2002-06-25T18:45:18Z </UCPTlastUpdate>
</Alarm>
</iLONAlarmGenerator>
</Result>
i.
LON 100 Internet Server Program
7-4
mer’s Reference