LON 100 Internet Server Programmer’s Reference

9-9

Property Description

<Point>

You can specify as many input data points as you want per Analog

Function Block. The input data points for an Analog Function Block are

defined by a list of <Point> elements in the <Data> parameter supplied to
the function.
For each element, you must specify an index number to be used within the

Analog Function Block (UCPTindex), the name of the data point
(UCPTpointName), and the interval to use when polling the data point’s

value (UCPTpollRate). The poll rate must be specified as an integer
between 0-6553. If the input data point is a structure, you must also

specify the name of the field to use when performing comparisons with the

data point (UCPTfieldName).

The value of the selected field for each input data point will be used to

generate a value for the output data point. This value assigned to the

output data point will vary, depending on the output function
(UCPToutputFunction) selected for the Analog Function Block.
NOTE: You should note that other

i.

LON 100 applications may cause the

Data Server to poll this data point’s value as well. The poll rate specified

by these applications should be compatible with each other. For example, if

an Analog Function Block is polling a data point every 15 seconds, and the
Data Logger is polling that data point every 10 seconds, then the Data

Server will have to poll the value of the data point every five seconds to

ensure that each application gets a current value for each poll.

It is important to note this as you set poll rates for various applications, as

you may end up causing more polls than is efficient on your network. For

example, if an Analog Function Block is polling a data point every 9
seconds and a Data Logger is polling a data point every 10 seconds, the

Data Server would have to poll the data point every second to ensure that

each application polls for a current value. This may create a significant
amount of undesired traffic.

<CompareDataPoint>

This element defines the compare data point this Analog Function Block
will use.
You must specify the name of the data point (UCPTpointName), the name
of the field to use when making comparisons with the data point

(UCPTfieldName) if it is a structure, and the interval to use when polling

the data point’s value (UCPTpollRate).

The value of this data point will be compared to the value of each input

data point when the output function selected for the Analog Function Block

is FN_COMPARE, FN_AND or FN_OR. The comparison to perform is
determined by the <UCPTcompFunction> property, and the result of this

comparison will be stored in the output data point.
This value will not be used in comparisons if the <UCPTtrueThreshold>
property is defined.