Echelon i.LON 100 e2 Internet Server User Manual

Page 190

Advertising
background image

i.

LON 100 Internet Server Programmer’s Reference

If the SNVT_scene Input Field Values

Are….

Then the SNVT_setting Output Field Values Are….

function scene_number

function setting Rotation

SC_RECALL 2

SET_STATE 50

0

SC_RECALL 3

SET_STATE 75

0

SC_RECALL >3

SET_NUL 100

0

SC_NUL N/A

SET_NUL

100

0

12.2.1.2.1.6 SNVT_scene_TO_SNVT_switch

Use this Type Translator Rule to translate an input data point of type SNVT_scene to an

output data point of type SNVT_switch. When you use this rule, you must reference the

SNVT_scene data point that is to be translated by its <UCPTpointName> in the
<InDataPoint> element. You must reference the SNVT_switch data point to store the result

of the translation by its <UCPTpointName> in the <OutDataPoint> element.
Each time a translation is made, the SNVT_switch output data point will be assigned a value
and state based on the values assigned to the function and scene_number fields of the

SNVT_scene input data point. The value assigned to the output data point follow the rules
described in Table 66.

Table 66 SNVT_scene to SNVT_switch

If the SNVT_scene Input Field Values Are....

scene_number

Then the SNVT_switch Output Data Point Will Be

Set To...

SC_NUL N/A* 0.0

0

SC_RECALL 1

25.0

1

SC_RECALL 2

50.0

1

SC_RECALL 3

75.0

1

SC_RECALL >3

100.0

1

SC_RECALL 255

0.0

0

function

*If the input function is SC_NUL and the input scene_number is 0, the value of the output data point
will not be modified.

12.2.1.2.1.7 SNVT_setting_TO_SNVT_switch

Use this Type Translator Rule to translate an input data point of type SNVT_setting to an

output data point of type SNVT_switch. When you use this rule, you must reference the
SNVT_setting input data point that is to be translated by its <UCPTpointName> in the

<InDataPoint> element. You must reference the SNVT_switch data point to store the result

of the translation by its <UCPTpointName> in the <OutDataPoint> element.

Each time a translation is made, the SNVT_switch output data point will be assigned a value

based on the values assigned to the function and setting fields of the SNVT_setting input

data point. The value assigned to the output data point follow the rules described in Table
67.

Table 67 SNVT_setting_TO_SNVT_switch

If the SNVT_setting Input Field Values Are....

Function setting

Then the SNVT_switch Output Data Point Will Be

Set To...

12-10