Alarmgeneratorget, Alarmgeneratorget -5, Alarmgeneratorget on – Echelon i.LON 100 e2 Internet Server User Manual

Page 94: 2 alarmgeneratorget

Advertising
background image

i.

LON 100 Internet Server Programmer’s Reference

7-5

7.2.1.2 AlarmGeneratorGet

You can use the AlarmGeneratorGet function to retrieve the configuration of any Alarm
Generator that you have added to the

i.

LON 100. You must reference the Alarm Generator

whose configuration is to be retrieved by its index number in the <Data> parameter you

supply to the function, as in the example below.

<Data> Parameter

<Data>
<iLONAlarmGenerator>
<Alarm>

<UCPTindex>1</UCPTindex>
</Alarm>
</iLONAlarmGenerator>
</Data>

<Result> Parameter

<Result>
<iLONAlarmGenerator>
<Alarm>

<UCPTindex>1</UCPTindex>

<UCPTlastUpdate>2004-05-14T19:21:39Z</UCPTlastUpdate>
<UCPTdescription>Heating Controller</UCPTdescription>
<UCPTfbName>Alarm Generator- 1</UCPTfbName>
<SCPTalrmIhbT>0 00:00:00.000</SCPTalrmIhbT>
<UCPTalarmPriority>PR_LEVEL_1</UCPTalarmPriority>
<UCPTpollOnResetDelay>0.0</UCPTpollOnResetDelay>
<UCPTpollRate>0.0</UCPTpollRate>
<UCPTalarm2Description>none</UCPTalarm2Description>
<InputDataPoint>

<UCPTpointName>NVL_nviTemp0</UCPTpointName>
</InputDataPoint>
<CompareDataPoint>

<UCPTpointName>NVL_nviTemp1</UCPTpointName>
</CompareDataPoint>
<AlarmDataPoint>

<UCPTpointName>NVL_nvoAlarm0</UCPTpointName>
</AlarmDataPoint>

<Alarm2DataPoint>

<UCPTpointName>NVL_nvoAlarm2</UCPTpointName>
</Alarm2DataPoint>

<UCPTcompFunction>FN_LIMIT

compFunction>

</UCPT

<UCPTalarmSetTime>0 00:00:00.000</UCPTalarmSetTime>
<UCPTalarmClrTime>0 00:00:00.000</UCPTalarmClrTime>
<UCPTlowLimit1Offset>4.0</UCPTlowLimit1Offset>
<UCPTlowLimit2Offset>8.0</UCPTlowLimit2Offset>

<UCPThighLimit1Offset>4.0</UCPThighLimit1Offset>
<UCPThighLimit2Offset>8.0</UCPThighLimit2Offset>
<SCPThystHigh1>2.0</SCPThystHigh1>
<SCPThystHigh2>2.0</SCPThystHigh2>
<SCPThystLow1>2.0</SCPThystLow1>
<SCPThystLow2>2.0</SCPThystLow2>
</Alarm>
</iLONAlarmGenerator>
</Result>

The function returns an <Alarm> element for each Alarm Generator referenced in the

<Data> parameter you supplied to the function. The properties contained within each

Advertising