Echelon i.LON 100 e2 Internet Server User Manual

Page 104

Advertising
background image

The following diagram depicts the four different alarm conditions, as well as the

corresponding hysteresis levels that must be reached to clear the alarms generated for each
condition, in a line chart.
Please note that the diagram uses enumerations to label the hysteresis levels the input value

must reach for each alarm status to be cleared. For example, AL_HIGH_LMT_CLR_2
represents the value necessary to clear the AL_HIGH_LMT_ALM_2 alarm status.

AL_HIGH_LMT_CLR_1 represents the value necessary to clear the AL_HIGH_LMT_ALM_1
alarm status. The data points in your network will not be updated to these statuses at any

time.

AL_HIGH_LMT_ALM_2

CompValue +
UCPThighLimit2Offset=
AL_HIGH_LMT_ALM2

CompValue +

UCPThighLimit2Offset

- SCPThystHigh2

AL_HIGH_LMT_CLR_2 **

AL_HIGH_LMT_ALM_1

CompValue +
UCPThighLimit1Offset=
AL_HIGH_LMT_ALM1

CompValue +

UCPThighLimit1Offset

- SCPThystHigh1

AL_NO_CONDITION

AL_HIGH_LMT_CLR_1 **

CompValue

AL_LOW_LMT_CLR_1 **

Input Value

CompValue –

UCPTlowLimit1Offset

+SCPThystLow1

AL_LOW_LMT_ALM_1

CompValue -
UCPTlowLimit1Offset=
AL_LOW_LMT_ALM1

AL_LOW_LMT_CLR_2 **

CompValue –

UCPTlowLimit2Offset

+SCPThystLow2

CompValue -
UCPTLowLimit2Offset=
AL_LOW_LMT_ALM2

AL_LOW_LMT_ALM_2

Figure 1

Hysteresis Levels and Offset Limits


i.

LON 100 Internet Server Programmer’s Reference

7-15