i

This technical data is valid for a new appliance with its

own heat exchangers.

6 Envirosorb

Description

Unit

7

12

14

Min. operating outside temperature (in heating)

°C

-20

-20

-20

Max. operating outside temperature (in heating)

°C

30

30

30

Specifi cations, with radiators
(fl ow : 45°C, return : 40°C, outside dry temperature (wet) 7 (6)°C)
Heating output

kW

7.4

12.95

14

Power input

kW

2.34

4.3

4.36

Rated electrical current

A

10

18.7

19

COP* A7(6) W45-40

3.16

3.01

3.21

Specifi cations, with underfl oor heating
(fl ow : 35°C, return : 30°C, outside dry temperature (wet) : 7 (6)°C)
Heating output

kW

7.2

11.9

14.5

Power input

kW

1.84

3.04

3.57

Rated electrical current

A

8

13.2

15.6

COP* A7(6) W35-30

3.91

3.91

4.06

Refrigerant circuit
Type of refrigerant
Quantity of refrigerant

kg

1.81

2.485

3.385

Type of compressor

Rotary

Type of oil

Polyolester

Type of regulator

Electronic

Fan speed

rpm

1000

805

1050

Maximum operating pressure (PS)

bar

45

45

45

Pa

45 x 10

5

45 x 10

5

45 x 10

5

Heat pump circuit

Max. supply pressure.

bar

3

3

3

Pa

3 x 10

5

3 x 10

5

3 x 10

5

Min. supply pressure

bar

0.5

0.5

0.5

Pa

50 x 10

3

50 x 10

3

50 x 10

3

Nominal water fl ow rate in heating mode

l/h

1200

2100

2500

Flow rate detection threshold

l/h

500

500

500

Min. volume of the installation

l

28

42

49

Max volume of heat pump circuit, without auxiliary tank, for a water outlet

temperature of 35°C

l

65

95

95

Minimum fl ow temperature setting (in heating)

°C

20

20

20

Maximum fl ow temperature setting (in heating)

°C

60

60

60

Volume of water in the heat pump

l

1.2

2.3

2.3

TECHNICAL DATA