Installation – Glow-worm Clearly Heat Pumps 14kW User Manual

Page 17

Advertising
background image

0020117819_01 - 05/11 - Glow-worm

- 15 -

2.3

Protection against the sharp edges of the sheet metal

for the cable passage (if necessary)

(x1)

2.4

Leak-tight seal for the cable passage (if necessary)

(x1)

3

Packet of documents

(x1)

3.1 Installation

manual

(x1)

3.2

Instructions for use

(x1)

4

Command unit

(x1)

Check the contents of the package.

9.2

Recommendations before installation

9.2.1

Design of the heating circuit

The heat emitters may be either low temperature (underfl oor

heating, etc.), or medium temperature (warm radiator, etc.).

b

We recommend that you provide suffi cient fl ow for the

temperature diff erence between fl ow and return to

be equal to 7 C for a underfl oor heating and 15 C for

radiators.

The route of the piping will be designed to take all measures ne-

cessary to avoid air pockets and facilitate the permanent venting

of the installation. Vents must be provided at each high point of

the pipes, and on all the radiators.

b

Always leave a radiator open.

We recommend installing a drainage valve at the lowest point of

the installation.

In the case of the use of thermostatic valves, it is imperative not

to fi t to all radiators, taking care to fi t these valves in rooms with

high input and never in rooms where the room thermostats are

installed.

- If it is an old installation, it is essential to rinse the radiator

circuit before installing the new appliance and to add an anti-

sludge fi lter.

- If a component of the system is not to be installed

immediately, protect the various connections so plaster

and paint cannot compromise the seal on the subsequent

connection.

Install the following components on the heating circuit return:

- a heating fi lter,

- 2 quarter-turn shut-off valves (1 each side of the fi lter),

- an air separator (if necessary),

- an anti-sludge fi lter (if necessary).

In the case of a underfl oor heating, install a security device to

prevent overheating, with manual reset (55°C) on the heating

circuit fl ow. Connect the overheating security device to the

glycol pump of the heat pump.

9.2.2

Design of the heat pump circuit

Installation pipework must be designed and installed to ensure

venting of air from the system is possible.

b

Ensure that the water fl ow rate of the water circuit

corresponds to the nominal water fl ow rate of the

appliance (see ¨Technical data¨ chapter).

Install the following components on the rear section of the

heat pump:

- a fi lter,

- a ¼ shut –off valve on each side of the fi lter,

- a drain valve,

- an air separator (if necessary)

- a sludge deposit (if necessary).

Install a ¼ turn shutoff valve in the fl ow of the heat pump.

i

In order to avoid the transmission of vibrations to

surrounding structures, use fl exible hoses for the

hydraulic connections at least 1 metre from the heat

pump.

b

Insulate the pipes with a UV- and hightemperature-

resistant insulation.

9.3 Dimensions

9.3.1 Envirosorb

7

150

150

600

908

326

821

INSTALLATION