Installation – Glow-worm Clearly Heat Pumps 14kW User Manual

Page 21

Advertising
background image

0020117819_01 - 05/11 - Glow-worm

- 19 -

Key

1 Heat

pump

2 Power supply and electrical protection for the heat pump (*)

3 Command unit for the heat pump

4 Glow Worm control unit (*)

5 Glow Worm hydraulic module (*)

6 Anti-sludge

fi lter (*)

A Flow heat pump circuit

B Return heat pump circuit

E

Return heating circuit

F

Flow heating circuit

H Discharge from the safety valve to a container for recovering glycol

water solution

(*) Not delivered with the appliance

Adjusting the heat pump's command unit

To fi nd out the description of each function,

see the chapter "Specifi c adjustment".

i

The setting of codes 112, 114, 117, 122, 123,

124, 125, 126 must be identical on the heat pump

command unit and the systempro control unit.

Menu

Name of the function

Value

Factory setting

100

Type of system regulation

2

2

101

Confi guration of the command unit

0

0

112

External calibrated adjustment graphs

7 - 12 (*)

8

114

ECO heating mode

1 - 20°C (*)

5°C

117

External calibrated adjustment graphs for cooling

0 (*)

2

122

Maximum reference exterior temperature

24 - 46°C (*)

40°C

123

Exterior temperature from which the heat pump stops in cooling mode

0 - 30°C (*)

22°C

124

Minimum temperature of water in the installation in cooling mode

4 - 20°C (*)

4°C

125

Maximum temperature of water in the installation in cooling mode

4 - 20°C (*)

12°C

126

Confi gurations exterior sensor

2

2

146

Confi guration for stopping the heat pump if control by S1 contact input

1

2

147

Confi guration of the output between terminal channels 5 and N

1

1

148

Limit exterior temperature (T0)

-20°C

-20°C

155

Functioning of main circulator

0

1

(*) Refer to the system installation manual for pairing the settings of these codes.

Application conditions

- Command unit used as confi guration tool (see the chapter

"Location of the appliance"),

- Installation with underfl oor heating (< 53°C) or low-

temperature radiator (<60°C),

i

For the dimensioning of the cables and the electrical

protection on the appliances, see the chapter

"Electrical connection".

Envirosorb

7

12

14

Minimum volume of the installation (l)

28

42

49

Max volume of heat pump circuit, without

additional vessel, for a water outlet temperature

of 35°C (l)

65

95

95

Volume of water in the heat pump

1.2

2.3

2.3

Nominal water fl ow rate (m³/h)

1.2

2.1

2.5

INSTALLATION

Advertising
This manual is related to the following products: