Installation – Glow-worm Clearly Heat Pumps 14kW User Manual

Page 34

Advertising
background image

0020117819_01 - 05/11 - Glow-worm

- 32 -

Predefi ned heating curves (code 112)

30

20

40

50

60

A

B

-20

-15 -10

-5

0

5

10

15

20

12

11

10

9

8

7

Key

7 Heating graph n°7

8 Heating graph n°8 (factory setting)

9 Heating graph n°9

10 Heating graph n°10

11 Heating graph n°11

12 Heating graph n°12

A Heating

fl ow temperature (°C)

B Exterior temperature (°C)

Code Function

Description

Setting

Factory

setting

Modifi able

parameter

Min

Max

112 Predefi ned heating

curves

0 = Personalised graph (see codes 118 to 121)

1 to 6 = Not used

7 to 12 = Pre-defi ned graphs (see above graphs)

1

12

8

Yes

114 ECO heating mode

Reduction off set for the installation's water temperature setting in heating mode.

1°C

20°C

5°C

Yes

116 ECO cooling mode

Increase off set for the installation's water temperature setting in cooling mode.

1°C

10°C

5°C

Yes

117

Not used

Personalised heating curves (codes 118, 119, 120, 121)

-20

-15 -10

-5

0

5

10

15

20

A

B

0

10

20

30

40

50

60

2

3

1

4

Key

1 Code

118

2 Code

119

3 Code

120

4 Code

121

A Heating

fl ow temperature (°C)

B Exterior temperature (°C)

Code Function

Description

Setting

Factory

setting

Modifi able

parameter

Min

Max

Setting codes 118 to 121 is necessary only if code 112 = 0.

118 Minimum reference

exterior temperature

Choose the minimum reference exterior temperature for the region where the

heat pump is installed.

-20°C 10°C

-7°C

Yes

119

Exterior temperature

from which the heat

pump stops in heating

mode

When the exterior temperature reaches the input value, heat pump stops.

Choose the exterior temperature from which the heat pump must stop in heating

mode.

10°C 30°C

20°C

Yes

120

Minimum temperature

of water in the

installation in heating

mode

Choose the minimum temperature of the water in the installation in heating

mode.

20°C 60°C

40°C

Yes

121

Maximum temperature

of the water in the

installation in heating

mode

Choose the maximum temperature of the water in the installation in heating

mode.

20°C 60°C

55°C

Yes

122

Not used

123

Not used

124

Not used

125

Not used

INSTALLATION