0020117819_01 - 05/11 - Glow-worm

- 29 -

Envirosorb 7 fl ow/pressure curves

A

B

0

10

20

30

40

50

60

720

1440

2160

2880

1

2

3

Key

1 Speed

I

2 Speed

II

3 Speed

III

A Available pressure (kPa)

B Flow in the circuit (l/h)

Envirosorb 12, Envirosorb 14 fl ow/pressure curves

A

B

0

10

20

30

40

50

60

70

80

720

1440

2160

2880

1

2

3

Key

1 Speed

I

2 Speed

II

3 Speed

III

A Available pressure (kPa)

B Flow in the circuit (l/h)

15.2 Settings for the command unit

15.2.1 Overall

view

1 2 3 4 5 6 7

14

1

2

3

7

6

5

4

10

9

8

13 12

11

Key

1 Selection of “standby” mode in the weekly programming

2 Hold the selected temperature or runs the scheduled program

3 Choice of functioning mode

4 Display

5 Scroll

up

6 Scroll

down

7 Validation

8 Temperature

Night

9 Temperature

Eco

10 Temperature

Comfort

11 Setting

day/time/minute

12 Programme: time when time interval begins

13 Programme: choice of time interval

14 Programme: group of days

15.2.2 Appliance

confi guration parameters

i

If the parameters are changed, it is important to leave

the control box connected for at least 10 seconds so

that the change is properly saved.

Press simultaneously on the button ( ) and (M) for 3

seconds. The parameter number is displayed and its value

blinks.

Press the button ( ) to access the parameter "302".

Press the button (M). The value of the parameter fl ashes.

Description of parameter 302

Setting

Factory

setting

Min

Max

0 = Cooling only

1 = Heating + cooling

2 = Heating only

0

2

2

Press the buttons (

) to modify the value.

Press the button (M) to confi rm the parameter setting.

i

The other parameters 301, 303, 304, 305 and 306

must not be modifi ed.

Press the button (OK) to exit the menu and validate the

settings.

15.2.3

Parameters set by the installer

This menu lets you enter the settings intended for the fi nal user.

Press simultaneously on buttons (

) and (

) for 3

seconds. The parameter number is displayed and its value

blinks.

Press the button (M) to access the parameter. The value of the

parameter fl ashes.

Press the buttons (

) to modify the value.

Press the button (M) to confi rm the parameter setting.

Press the buttons (

) to move to the next parameter.

Perform the previous operations again for the other

parameters.

Press the button (OK) to exit the menu and validate the

settings.