10.2 Horizontal Telescopic Flue - A2043600

Refer to diagram 10.2 for kit contents.

10.3 REAR Flue

If a wall thickness is between 231mm min. to 441mm max.

then the flue can be used without extensions.
Remove the top flue outlet cover secured with four screws,

see diagram 10.4.
Using these screws inserted into the same holes on the boiler,

temporarily

secure the

flue elbow, measure the distance from

the outside wall to the butt joint, see diagram

10.5.

If the

measurement ‘Y’ exceeds 525mm, then the appropriate length

of extension pipe is required.
If the dimension is less than 315mm DO NOT cut the flue, it

can project to a maximum of 600mm, refer to diagram 10.6. If

this is not desirable then a Standard flue MUST be used and

cut to length.

10.4 SIDE Flue

Remove the top flue outlet cover secured with four screws,

see diagram 10.4.
Using these screws inserted into the same holes on the boiler,

temporarily

secure the

flue elbow, measure the distance from

the outside wall to the butt joint, see diagram 10.7. If the

measurement ‘Y’ exceeds 525mm, then the appropriate length

of extension pipe is required.
If the dimension is less than 315mm DO NOT cut the flue, it

can project to a maximum of 600mm, refer to diagram 10.6. If

this is not desirable then a Standard flue MUST be used and

cut to length.

Diagram 10.6

12979

10 Telescopic Flue - Length, Preparation and Installation