10 Direct Rear Flue - Length, Preparation and Installation

Secure clamping

band grips at

three positions

with screws

provided

Method (1)

Secure clamping

band in position

Method (2)

10.11 Direct Rear flue - Telescopic

Part No. A2043500.

Refer to diagram 10.19 for kit contents.

10.12 Flue Length

Measure the distance from the outside wall to the inside wall

face. This measurement must not exceed 512mm (465mm

if the upward piping kit is used). If the dimension is less than

291mm DO NOT cut the flue, it can project to a maximum of

600mm, see diagram 10.15.

10.13 Flue Fitting

Set the flue to the required length ‘Y’ plus 24mm min to 28mm

max, see diagram 10.20, ensure the air duct seams line up.

Mark the securing hole position in the air duct. Drill a 3mm

diameter hole at this position, take care not to pierce the

inner flue duct. Secure with screw provided and tape the joint,

see diagrams 10.19.
Fit the sealing collar onto the locating ring on the flue terminal,

see diagram 10.19.
Push the telescopic terminal assembly into the wall, externally

or internally, initially.
Draw the telescopic flue through the wall and engage the

telescopic terminal assembly into the clamping band grips.

The telescopic terminal assembly must be pulled forward of

the clamping band grips by the dimension shown in diagram

10.21 to ensure a good seal when the boiler is located onto

the fixing plate.
Ensure the correct alignment of the terminal.
There are two alternative methods of securing the flue:-
Method (1) There are six holes provided in the clamping band

grips, three of these should be used to secure the flue. Mark

and drill 3mm holes in the air duct then secure to the clamping

grip with the screws provided.
Method (2) Secure the telescopic terminal assembly using the

clamping band supplied. The position of the clamping band

securing screw is important, refer to label and wall template.
IMPORTANT: CHECK THE CLAMPING BAND IS

SUFFICIENTLY TIGHTENED TO AVOID ANY MOVEMENT

OF THE FLUE WHEN FITTING THE BOILER.
Continue at the appropriate paragraph of section 7.

Diagram 10.20

14809

Diagram 10.21

14808

15419

Diagram 10.19